Product specs, Roduct, Pecifications – Goodman Mfg GPH15M User Manual
Page 3

P
roduct
S
PecificationS
P
roduct
S
PecificationS
SS-GPH15M
www.goodmanmfg.com
3
s
peCifiCations
GPH15
24M41A*
GPH15
24M41B*
GPH15
30M41A*
GPH15
30M41B*
GPH15
36M41A*
GPH15
36M41B*
Cooling Capacity
Total BTU/h
24,000
24,000
29,000
29,000
35,400
35,400
Sensible BTU/h
18,000
18,000
22,200
22,200
26,700
26,700
SEER / EER
15.0/ 12.0
15.0/ 12.0
14.5/ 11.5
14.5/ 11.5
14.5/ 11.5
14.5/ 11.5
Decibels
76
76
76
76
76
76
AHRI #s
4385138
5677908
4385139
5677909
4385140
5677910
Heating Capacity
BTU/h (47°F)
23,400
23,400
27,400
27,400
35,400
35,400
C.O.P (47°F)
3.6
3.6
3.5
3.5
3.4
3.4
BTU/h (17°F)
12,400
12,400
15,200
15,200
18,600
18,600
C.O.P (17°F)
2.0
2.0
2.2
2.2
2.4
2.4
HSPF
8.0
8.0
8.0
8.0
8.0
8.0
Evaporator Motor
Type
EEM
EEM
EEM
EEM
EEM
EEM
Wheel (D x W)
10 x 9
10 x 9
10 x 9
10 x 9
10 x 9
10 x 9
Nominal Cooling CFM
860
860
1,000
1,000
1,200
1,200
FLA
4.1
4.1
4.1
4.1
4.1
4.1
No. of Speeds
5
5
5
5
5
5
Horsepower - RPM
½ -1,050
½ -1,050
½ -1,050
½ -1,050
½ -1,050
½ -1,050
Evaporator Coil
Face Area (ft²)
4.5
4.5
4.5
4.5
4.5
4.5
Rows Deep/ Fin per Inch
3/ 14
3/ 14
3/ 14
3/ 14
4/ 14
4/ 14
Expansion Device
TXV
TXV
TXV
TXV
TXV
TXV
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
¾"
R-410A Refrigerant Charge (oz.)
113
113
128
128
174
174
Condenser Fan / Coil
Horsepower - RPM
¼ - 850
¼ - 850
¼ - 850
¼ - 850
¼ - 850
¼ - 850
FLA/LRA
1.5/ 3.0
1.5/ 3.0
1.5/ 3.0
1.5/ 3.0
1.5/ 3.0
1.5/ 3.0
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
Face Area (ft²)
17.2
17.2
17.2
17.2
17.2
17.2
Rows Deep/ Fin per Inch
1 / 22
1 / 22
1 / 22
1 / 22
2 / 16
2 / 16
Compressor
Quantity
1
1
1
1
1
1
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Stage
Single
Single
Single
Single
Single
Single
Electrical Data
Voltage/ Phase/ Hz
208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60
Compressor RLA/ LRA
12.8 / 58
12.8 / 58
14.1 / 73
14.1 / 73
16.7 / 79
16.7 / 79
Indoor Blower FLA
4.1
4.1
4.1
4.1
4.1
4.1
Total Unit Amps
18.4
18.4
19.7
19.7
22.3
22.3
Min. Circuit Ampacity¹
21.6
21.6
23.2
23.2
26.5
26.5
Max. Overcurrent Protection²
30
30
35
35
40
40
Shipping Weight (lbs)
376
376
385
385
438
438
¹
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
²
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.