beautypg.com

Expanded heating data, Xpanded, Eating – Goodman Mfg GPH15M User Manual

Page 21: Roduct, Pecifications

background image

P

roduct

S

PecificationS

P

roduct

S

PecificationS

SS-GPH15M

www.goodmanmfg.com

21

e

xpanded

h

eating

d

ata

GPH1524M41**

Outdoor Ambient Temperature

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

29.4 27.8 26.2 24.5

23.4 22.7 21.1 19.4

15.6 14.4 13.2 12.5

12.0 10.8

9.6

8.4

7.1

5.8

∆T

31.7 30.0 28.2 26.4

25.2 24.4 22.7 20.9

16.8 15.5 14.3 13.5

13.0 11.6 10.3

9.0

7.7

6.3

kW

2.08 2.04 2.00 1.96

1.94 1.92 1.88 1.84

1.81 1.77 1.73 1.71

1.69 1.65 1.61 1.57

1.53 1.49

Amps

10.8 10.2

9.6

9.2

8.9

8.8

8.4

8.0

7.8

7.5

7.2

7.1

7.0

6.8

6.4

6.2

5.8

5.4

COP

4.14 4.00 3.84 3.66

3.54 3.46 3.28 3.09

2.52 2.38 2.24 2.15

2.09 1.92 1.74 1.56

1.36 1.15

EER

14.2 13.7 13.1 12.5

12.1 11.8 11.2 10.6

8.6

8.1

7.7

7.3

7.1

6.6

6.0

5.3

4.7

3.9

HI PR

388

372

358

342

334

328

315

302

290

277

266

259

255

245

235

226

218

210

LO PR

145

134

126

115

109

105

96

86

77

69

61

57

55

46

40

34

29

23

GPH1530M41**

Outdoor Ambient Temperature

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

34.4 32.6 30.7 28.7

27.4 26.6 24.7 22.7

18.8 17.4 16.0 15.1

14.5 13.0 11.6 10.1

8.6

7.1

∆T

31.9 30.2 28.4 26.6

25.4 24.6 22.8 21.1

17.4 16.1 14.8 14.0

13.5 12.1 10.7

9.3

8.0

6.5

kW

2.31 2.27 2.22 2.18

2.15 2.13 2.09 2.04

2.08 2.03 1.98 1.95

1.93 1.89 1.84 1.79

1.74 1.69

Amps

11.4 10.7 10.0

9.5

9.2

9.0

8.5

8.2

7.8

7.5

7.2

7.1

7.0

6.7

6.3

6.0

5.6

5.1

COP

4.36 4.21 4.04 3.86

3.73 3.65 3.46 3.26

2.65 2.51 2.36 2.26

2.20 2.03 1.84 1.65

1.45 1.22

EER

14.9 14.4 13.8 13.2

12.8 12.5 11.8 11.2

9.1

8.6

8.1

7.7

7.5

6.9

6.3

5.6

4.9

4.2

HI PR

383

368

353

338

330

324

311

299

286

273

262

256

251

242

233

223

215

208

LO PR

138

128

120

110

104

100

92

82

74

66

58

54

52

44

38

32

28

22

GPH1536M41**

Outdoor Ambient Temperature

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

44.6 42.2 39.8 37.2

35.5 34.4 32.0 29.5

23.2 21.4 19.7 18.6

17.9 16.1 14.3 12.4

10.6

8.7

∆T

34.4 32.6 30.7 28.7

27.4 26.5 24.7 22.7

17.9 16.5 15.2 14.4

13.8 12.4 11.0

9.6

8.2

6.7

kW

3.24 3.18 3.11 3.05

3.01 2.98 2.92 2.85

2.43 2.37 2.32 2.29

2.26 2.21 2.15 2.10

2.04 1.99

Amps

17.4 16.2 15.3 14.5

14.1 13.9 13.2 12.6

12.2 11.7 11.3 11.1

10.9 10.5

9.9

9.5

8.9

8.3

COP

4.03 3.89 3.74 3.57

3.45 3.38 3.21 3.02

2.80 2.64 2.49 2.38

2.32 2.13 1.94 1.73

1.52 1.28

EER

13.8 13.3 12.8 12.2

11.8 11.5 11.0 10.3

9.6

9.0

8.5

8.1

7.9

7.3

6.6

5.9

5.2

4.4

HI PR

454

435

418

400

390

383

368

353

338

323

310

303

297

286

275

264

254

245

LO PR

137

127

119

109

103

99

91

81

73

65

57

53

52

44

38

32

28

22

GPH1543M41**

Outdoor Ambient Temperature

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

50.2 47.5 44.7 41.8

39.9 38.7 35.9 33.1

23.2 21.4 19.7 18.6

17.9 16.1 14.3 12.4

10.6

8.7

∆T

38.7 36.6 34.5 32.2

30.8 29.8 27.7 25.6

17.9 16.5 15.2 14.4

13.8 12.4 11.0

9.6

8.2

6.7

kW

3.45 3.38 3.31 3.24

3.20 3.17 3.10 3.03

2.43 2.37 2.32 2.29

2.26 2.21 2.15 2.10

2.04 1.99

Amps

18.5 17.3 16.3 15.5

15.0 14.8 14.0 13.4

12.9 12.5 12.0 11.7

11.6 11.1 10.5 10.0

9.4

8.7

COP

4.25 4.11 3.95 3.77

3.65 3.57 3.39 3.20

2.80 2.64 2.49 2.38

2.32 2.13 1.94 1.73

1.52 1.28

EER

14.5 14.0 13.5 12.9

12.5 12.2 11.6 10.9

9.6

9.0

8.5

8.1

7.9

7.3

6.6

5.9

5.2

4.4

HI PR

413

395

380

364

355

348

335

321

308

294

282

275

271

260

250

240

231

223

LO PR

143

133

125

114

108

104

96

85

77

69

60

56

54

46

39

33

29

23

Notes:

Above information is for nominal CFM and 70-degree indoor dry bulb. Instantaneous capacity listed.

High pressure is measured at the liquid line access fitting.

Amps: Unit amps (comp.+ evaporator motor + condenser fan motor)

Low pressure is measured at the compressor suction access fitting.

kW = Total system power