Heat kit eloectrical data, Lectrical, Lower – Goodman Mfg GPH15M User Manual
Page 27: Roduct, Pecifications

P
roduct
S
PecificationS
P
roduct
S
PecificationS
SS-GPH15M
www.goodmanmfg.com
27
h
eat
k
it
e
leCtriCal
d
ata
(B
lower
o
nly
, h
eat
m
ode
)
Model and
Heat Kit Usage
Circuit #1
Circuit #2
Single-Point Kit
Actual kW /
BTU@ 240V
MCA¹
MOP²
MCA¹
MOP²
MCA¹
MOP²
GPH1524M41**
5.4
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
46
50
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
58
60
7.0 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
71
80
9.5 / 32,400
GPH1530M41**
5.4
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
48
50
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
60
60
7.0 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
73
80
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
97
100
14.25 / 48,600
GPH1536M41**
5.4
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
51
60
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
63
70
7.0 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
76
80
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
101
110
14.25 / 48,600
GPH1543M41**
3.6
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
51
60
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
63
70
7.0 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
76
80
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
101
110
14.25 / 48,600
GPH1549M41**
3.6
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
56
70
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
67
80
7.00 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
80
90
9.50 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
105
110
14.25 / 48,600
HKP-20C*
43 / 49
45 / 50
43 / 49
45 / 50
132
150
19.0 / 64,800
GPH1560M41**
8.8
---
---
---
--
--
---
HKR-05*, HKR-05C*
21 / 25
25 / 25
---
---
67
80
4.75 / 16,200
HKR-08*, HKR-08C*
32 / 36
35 / 40
---
---
79
90
7.0 / 23,800
HKR-10*, HKR-10C*
43 / 49
45 / 50
---
---
92
100
9.5 / 32,400
HKP-15C*
43 / 49
45 / 50
21 / 25
25 / 25
116
125
14.25 / 48,600
HKP-20C*
43 / 49
45 / 50
43 / 49
45 / 50
144
150
19.0 / 64,800
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protection Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker option
^ Heat Kit requires three-phase power supply
Note: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respectively to meet new UL1995 requirements.