GPG13(36)3** WIRING DIAGRAM

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

2 STAGE COOLING WITH ECONOMIZER

OPTION

HPS

BL/PK BLUE/PINK

HPS

HIGH PRESSURE SWITCH

0140G01001 REV. A

ALS

COMPONENT LEGEND

FC

F

EM

CH

C

CM

COMP

FAN CAPACITOR

FUSE

CONTACTOR

COMPRESSOR

CRANKCASE HEATER

CONDENSER MOTOR

AUXILIARY LIMIT SWITCH

EVAPORATOR MOTOR

LOW VOLTAGE

HIGH VOLTAGE

FIELD WIRING

LOW VOLTAGE

LINE VOLTAGE

OPTIONAL HIGH VOLTAGE

FACTORY WIRING

208-230/3/60

RS

PS

PLF

LS

IGN

IIC

GV

GND

ROLLOUT SWITCH

LIMIT SWITCH

GAS VALVE

IGNITOR

VM

NOTES

VENT MOTOR

TR

TRANSFORMER

EQUIPMENT GROUND

PRESSURE SWITCH

FEMALE PLUG/CONNECTOR

INTEGRATED IGNITION CONTROL

3 SPEED MOTOR

BK - HIGH SPEED

TERMINAL (IIC)

RD - LOW SPEED

USE NEC CLASS 2 WIRE.

6. USE COOPER CONDUCTORS ONLY.

THERMOSTAT FIELD WIRING

BL - MEDIUM SPEED

3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS.

BL BLUE

BK BLACK

OR ORANGE

GR GREEN

PU PURPLE

PK PINK

WH WHITE

RD RED

BR BROWN

YL YELLOW

TO BLOWER HOUSING IN RETURN AIR COMPARTMENT.

5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT

SPEED AT COOL TERMINAL (IIC). CHANGE HEATING SPEED AT HEAT

4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING

FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.

2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE

INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY).

1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF

Y1

G

W

R

Y2

C

PU

GR

WH

RD

Y

R

G

W

BL

YL

RD

GR

WH

NO
ECONOMIZER

BL

FS

WIRE CODE

FLAME SENSOR

L3

L2

FC

T3

C

CM

C

CH

T2

F

C

T3

T2

T1

T1

NOTE 3

208-230/3/60

SUPPLY VOLTAGE

L1

IIC

C

1

V

M

NOTE 2

E

M

G
V

RS

2

3

T
R

C

H

LS

AL

S

FS

3

IG

N

FS

C

3

2

5

6

PLF

C

NOTE 5

PS

6

8

10

11

12

Y/Y2

W

Y1

INSTALLER/SERVICEMAN

L1

1

4

F

5

IIC

9

R

G

7

-

CHECK

GAS FLOW

CHECK

CHECK

GAS VALVE

BAD SWITCH

FLAME SENSOR

AUX. LIMIT OPEN

FLAME ROLLOUT

PRESSURE SWITCH

PRESSURE SWITCH

GAS PRESSURE

FAULT

NO POWER OR

OR

SWITCH

OPEN

SWITCH

OPEN ROLLOUT

OR

INTERNAL CONTROL

NORMAL OPERATION

IGNITION FAILURE

EQUIP. STATUS

OPEN AUX. LIMIT

PRESSURE SWITCH

WITHOUT INDUCER ON

3 MIN. COMP.

BAD SWITCH

COMPRESSOR

OUTPUT DELAY

FALSE FLAME SENSED

MAIN LIMIT OPEN

OPEN LIMIT SWITCH

ON

OFF

1 BLINK

5 BLINKS

4 BLINKS

STATUS LIGHT

2 BLINKS

6 BLINKS

3 BLINKS

(MED)

NOTE 4

2

4

1

C