3. SETTINGS

18

DBF Breaker Failure Protection

GEK-106168E

Common to all tables

Range

Default

Step

Oscillography Mask

Prefault Cycles

2-10

4

1

Arc Detection

Enable-Disable

Enable

Pickup

Enable-Disable

Enable

1

st

Stage trip

Enable-Disable

Enable

2

nd

Stage Trip

Enable-Disable

Enable

50BF A Trip

Enable-Disable

Enable

50BF B Trip

Enable-Disable

Enable

50BF C Trip

Enable-Disable

Enable

50BF 3P Trip

Enable-Disable

Enable

External Trigger

Enable-Disable

Enable

Communications Trigger

Enable-Disable

Enable

Hi-Set A Pickup

Enable-Disable

Enable

Hi-Set B Pickup

Enable-Disable

Enable

Hi-Set C Pickup

Enable-Disable

Enable

50BF A Init.

Enable-Disable

Enable

50BF B Init.

Enable-Disable

Enable

50BF C Init.

Enable-Disable

Enable

Lo-Set A Pickup

Enable-Disable

Enable

Lo-Set B Pickup

Enable-Disable

Enable

Lo-Set C Pickup

Enable-Disable

Enable

3P 50BF Init.

Enable-Disable

Enable

Neutral Pickup

Enable-Disable

Enable

Arc A Pickup

Enable-Disable

Enable

Arc B Pickup

Enable-Disable

Enable

Arc C Pickup

Enable-Disable

Enable

Functions Permitted

50BF 1P function

Permitted-Non-Permitted

Non-Permitted

50 BF 3P Function

Permitted-Non-Permitted

Non-Permitted

3P No I Function

Permitted-Non-Permitted

Non-Permitted

Independent for each table

Range

Default

Step

50BF Settings

PH Hi-Set Pickup

1-12A

2A

0.01A

PH Lo-Set Pickup

1-12A

1A

0.01A

Neutral Pickup

0.50-6A

1A

0.01A

1 Phase Timer T1

0.05-2s

0.5s

0.01s

3 Phase Timer T2

0.05-2s

1s

0.01s

3P No I Timer T3

0.05-2s

2s

0.01s

BF Logic (3P/2P)

2-Phases/3 Phases

2-Phases

Severe Fault 3P

Permitted-Non-Permitted

Non-Permitted

Low Load 2P

Permitted-Non-Permitted

Non-Permitted

Output Stages number

1-2

1

1

2nd Stage Timer

0.05-2s

2s

0.01s

Internal Arc Settings

Internal Arc Pickup

0.05-1A

1A

0.01A

Internal Arc Timer

0.10-2s

1s

0.01s