Airflow data, 15 t, Irflow – Goodman Mfg SS-CPG180-240 User Manual
Page 9: Roduct, Pecifications

SS-CPG180-240
www.goodmanmfg.com
9
P
roduct
S
PecificationS
a
irFlow
d
aTa
— 15 T
ons
Standard Belt Drive
ESP
In" H₂O
Turns Open
0
1
2
3
4
5
6
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
---
---
---
---
---
---
---
0
6,827
2.6675
6,394
2.2792
5,982
1.9434
0.4
---
---
---
---
7,079
3.2019
6,623
2.7551
6,161
2.3441
5,706
1.9787
5,271
1.6650
0.6
---
---
6,903
3.3168
6,405
2.8302
5,923
2.4063
5,434
2.0191
4,949
1.6776
---
---
0.8
6,717
3.4193
6,198
2.9169
5,668
2.4546
5,152
2.0544
---
---
---
---
---
---
1.0
5,975
2.9894
5,418
2.5110
---
---
---
---
---
---
---
---
---
---
1.2
5,147
2.5507
---
---
---
---
---
---
---
---
---
---
---
---
High-Static Belt Drive
ESP
In" H₂O
Turns Open
0
1
2
3
4
5
6
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
1.0
---
---
---
---
---
---
---
---
6,690
3.6895
6,008
3.0189
5,321
2.4323
1.2
---
---
---
---
---
---
6,653
3.9517
5,922
3.2198
5,182
2.5787
---
---
1.4
---
---
---
---
6,634
2.8014
5,857
3.4408
5,056
2.7377
---
---
---
---
1.6
---
---
6,638
4.5544
5,808
2.4260
4,948
2.9127
---
---
---
---
---
---
1.8
6,683
4.9263
5,784
3.9520
4,855
2.0548
---
---
---
---
---
---
---
---
2.0
5,803
4.2723
4,788
3.3189
---
---
---
---
---
---
---
---
---
---
Notes
• Airflow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
• Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applica-
tion that exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton.
• High-static airflow requires installation of high kit (HSKT240) or factory-built high-static model.
• Unit factory shipped with the sheave set at 2.5 turns open.