beautypg.com

Specifications, 15 t, Roduct – Goodman Mfg SS-CPG180-240 User Manual

Page 3: Pecifications

background image

SS-CPG180-240

www.goodmanmfg.com

3

P

roduct

S

PecificationS

p

rodUCT

s

peCiFiCaTions

— 15 T

ons

CPG180

3503B***B*

CPG180

3504B***B*

CPG180

3507B***B*

Cooling Capacity
Total, BTU/h

180,000

180,000

180,000

Sensible BTU/h

127,500

127,500

127,500

EER / IEER

10.8 / 11.0

10.8 / 11.0

10.8 / 11.0

Decibels

88

88

88

AHRI Reference #s

5197871

5197871

5197871

Heating Capacity
High Input / Output (KBTU/h)

350 / 280

350 / 280

350 / 280

Low Input / Output (KBTU/h)

262.5 / 210

262.5 / 210

262.5 / 210

Steady State Efficiency (%)

80

80

80

Temperature Rise Range (°F) High/Low

30-60 / 20-50

30-60 / 20-50

30-60 / 20-50

No. of Burners

7

7

7

Evaporator Motor / Coil
Motor Type (Belt Drive)

Std Static

Std Static

Std Static

Indoor Nominal CFM

5,400

5,400

5,400

Indoor Motor FLA (Cooling)

12.7

6.4

5.1

Horsepower - RPM

5.0 - 1,725

5.0 - 1,725

5.0 - 1,725

Metering Device

TXV

TXV

TXV

Filter Size (#)

20 x 25 x 2 (6)

20 x 25 x 2 (6)

20 x 25 x 2 (6)

Drain Size (NPT)

1"

1"

1"

R-410A Refrigerant Charge Cir #1

186.2

186.2

186.2

R-410A Refrigerant Charge Cir #2

170.8

170.8

170.8

Evaporator Coil Face Area (ft²)

20

20

20

Rows Deep / Fins per Inch

4 / 16

4 / 16

4 / 16

Belt Drive Evap Fan Data
# of Wheels (D x W)

2 (15" x 12")

2 (15" x 12")

2 (15" x 12")

Motor Sheave

1VP50 x 1⅛"

1VP50 x 1⅛"

1VP50 x 1⅛"

Blower Sheave / Belt

BK90 x 1³/₁₆" / BX42

BK90 x 1³/₁₆" / BX42

BK90 x 1³/₁₆" / BX42

Condenser Fan / Coil
Quantity of Condenser Fan Motors

3

3

3

Horsepower - RPM

⅓ - 1,075

⅓ - 1,075

⅓ - 1,075

Fan Diameter / # Fan Blades

22 / 3

22 / 3

22 / 3

Outdoor Nominal CFM

7,200

7,200

7,200

Face Area (ft²)

53.3

53.3

53.3

Rows Deep / Fins per Inch

2 / 27

2 / 27

2 / 27

Compressor
Quantity / Type

2 / Scroll

2 / Scroll

2 / Scroll

Compressor RLA / LRA CIR. #1

25 / 164

12.2 / 100

9.0 / 78

Compressor RLA / LRA CIR. #2

25 / 164

12.2 / 100

9.0 / 78

Electrical Data / Static
Voltage / Phase / Frequency

208-230/3/60

460/3/60

575/3/60

Standard Max Static

1.2

1.2

1.2

Outdoor Fan FLA / LRA

2.4 / 5.2

1.2 / 2.6

.9 / 2.2

Total Unit Amps

69.9

34.4

25.8

Min. Circuit Ampacity¹

76

38

28

Max. Overcurrent Protection (amps)²

100

45

35

Entrance Power Supply

2⅛"

2⅛"

2⅛"

Entrance Control Voltage

⅞"

⅞"

⅞"

Operating / Shipping Weight (lbs)

2083/ 2198

2083/ 2198

2083/ 2198

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

² May use fuses or HACR-type circuit breakers of the same size as noted.

Notes

• Always check the S&R plate for electrical data on the unit being installed.

• When a factory installed convenience outlet is installed in the equipment the unit MCA will increase by 7.5A for 208/230V units,

increase by 3.75A for 460V units and by 3A for 575V units. The MOP device must be sized accordingly.