Appendix B.3. Panel Power-up, Restarts and Resets
When the panel powers up or is restarted it will send an event on zone/circuit 69 device 0.
When the panel is reset from the Hot Keys on the front panel, it will send an event on zone/circuit 90, device 9.
The Client driver will clear all the Secutron_Type=device and Secutron_Type=function Data Arrays when it traps
any of these 2 events, provided the circuit 69 and 90 Map Descriptors have been set up as per the example Map
Descriptors under the Client Side configuration instructions.
Other events for Circuits 69 and 90 are shown below for which a bit will be set in the Secutron_Type=device Map
Descriptor’s Data Array at the device offset values shown below:
Circuit
Events
Program Restart
(Circuit 69)
000 – Power On/Hard reboot 003 – Illegal Instruction
001 - Watchdog
004 – Unused Interrupt
002 – Clock Monitor
005 – Orphan Interrupt
Hot Key Activation
(Circuit 90)
Function number of the Hot Key pressed.
001 – Fire Drill
026– Switch 11 On
002 - Lamp Test
027 – Switch 12 On
003 – Releaser Disconnect
028 – Switch 13 On
004 – Relay disconnect
029 – Switch 14 On
005 – Test mode
030 – Switch 15 On
006 – Signal Disconnect
031 – Switch16 On
007 - Acknowledge
032 – Switch 1 Off
008 – Signal Silence
033 – Switch 2 Off
009 - Reset
034 – Switch 3 Off
010 – Common Disconnect
035 – Switch 4 Off
011 – General Alarm
036 – Switch 5 Off
012 - Halt
037 – Switch 6 Off
013 - Abort
038– Switch 7 Off
013 – 2
nd
Stage Inhibit
039– Switch 8 Off
016 – Switch 1 On
040– Switch 9 Off
017 – Switch 2 On
041– Switch 10 Off
018 – Switch 3 On
042– Switch 11 Off
019 – Switch 4 On
043 – Switch 12 Off
020 – Switch 5 On
044 – Switch 13 Off
021 – Switch 6 On
045 – Switch 14 Off
022– Switch 7 On
046 – Switch 15 Off
023– Switch 8 On
047 – Switch16 Off
024– Switch 9 On
051 – Manual Restart
025– Switch 10 On