Configuring the FieldServer as a Honeywell Zellweger IR-148 Server
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to report sensor
data to Honeywell Zellweger IR-148 Client. As a Server this driver sends Gas value, Alarm, Trouble and Lock point
messages. The driver can be locked to send data for only one particular sensor.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for Honeywell Zellweger IR-148 communications, the driver independent FieldServer buffers need
to be declared in the “Data Arrays” section, the FieldServer virtual Node(s) needs to be declared in the “Server Side
Nodes” section, and the data to be provided to the Clients needs to be mapped in the “Server Side Map
Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
6.1
SERVER SIDE CONNECTION DESCRIPTORS
Section Title
Connections
Column
Title
Function
Legal Values
Port
Specify which port the device is connected to the
FieldServer
P1-P8 (with 232/485 converter), R1-
R2
3
Protocol
Specify protocol used
InfraTox or Infra-Tox
Baud*
Specify baud rate
19200 (Vendor limitation)
Parity*
Specify parity
None (Vendor limitation)
Data_Bits*
Specify data bits
8 (Vendor limitation)
Example
// Server Side Connections
Connections
Port , Protocol , Baud
, Parity , Data_Bits
R1
, InfraTox
, 19200 , None
, 8
3
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.