Appendix a. useful features, Appendix a.1. how data is stored by the driver, Appendix a.1.1 – FieldServer Honeywell Zellweger IR-148 User Manual
Page 14: Appendix a.1.2, Extended storage
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual
Page 14 of 17
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Appendix A. Useful Features
Appendix A.1. How Data is stored by the Driver.
Appendix A.1.1.
One Set of consecutive Data Array elements per point/sensor.
Offset Sensor Contents
Description
0
1
Alarm or Trouble
Set non-zero if alarm or a trouble has been reported. Set to zero if
neither are currently being reported.
1
1
Alarm Type
0 = None
1 = Caution
2 = Warning
3 = Alarm
2
1
Trouble
0 = None
1 = Trouble
3
1
Gas Value
Gas value multiplied by 100. If configured, scaling will be applied.
4
1
Gas Units
1
st
3 bytes of gas units are written as ASCII characters.
5
1
Gas Units
6
1
Gas Units
7
1
State
0 = Enabled
1 = Disabled
8
1
Gas Value Valid
1 = Gas Value updated with most recent message.
0 = Gas Value not updated.
9
1
Gas Value Age
In seconds since last update. Initial (and max) value = 0xffff
10
1
Sensor Data Age
Time since last message containing data about this sensor.
In seconds since last update. Initial (and max) value = 0xffff
11..21 2
22..32 3
33..43 4
44..54 5
55..65 6
66..76 7
77..87 8
Appendix A.1.2.
Extended storage
Offset
Sensor
Contents
Description
0
1
Alarm or Trouble
Non-zero if alarm or a trouble has been reported.
Zero if neither are currently being reported.
1
1
Alarm Type
0 = None, 1 = Caution, 2 = Warning, 3 = Alarm
2
1
Trouble
0=None, 1=Trouble
3
1
Gas Value
Gas value multiplied by 100 is stored here. When stored, if
configured, scaling will be applied.
4
1
Gas Units
1
st
3 bytes of gas units are written here as ASCII characters.
5
1
Gas Units
6
1
Gas Units
7
1
State
0 = Enabled, 1 = Disabled
8
1
Gas Value Valid
1 = Gas Value updated with most recent message.
0 = Gas Value not updated.
9
1
Gas Value Age
In seconds since last update.
Initial (and max) value = 0xffff
10
1
Sensor Data Age
Age since last message, containing data from this sensor in
seconds. Initial (and max) value = 0xffff
11
1
I/O State
255 = unknown, 0=Warm up, 1 = Ready, 2 = Trouble, 3=