6.2

SERVER SIDE NODE DESCRIPTORS

Section Title
Nodes
Column Title

Function

Legal Values

Node_Name

Provide name for Node

Up to 32 alphanumeric
characters

Node_ID

Irrelevant for this driver when only one Node is connected.
Otherwise the Node-ID should be the number of
points/sensors for which the Zellweger unit is configured. A
unique Node_ID is recommended for each Zellweger Unit as
it may be useful in exposing Node status information

0-255

Protocol

Specify protocol used

InfraTox, Infra-Tox.

Port

Specify at which port the device is connected to the
FieldServer
Ports P1-P8 require a 232/485 converter.

P1-P8

4

, R1-R2


Example

// Server Side Nodes

Nodes

Node_Name , Node_ID , Protocol , Port
DEVR1

, 1

, InfraTox

, R1

4

Ports P1-P8 require a 232/485 converter.