Configuring the FieldServer as a Honeywell Zellweger IR-148 Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate
with a Honeywell Zellweger IR-148 Server having one or eight sensors.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for Honeywell Zellweger IR-148 communications, the driver independent FieldServer buffers need
to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client
Side Nodes” section, and the data required from the Servers needs to be mapped in the “Client Side Map
Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1

CLIENT SIDE CONNECTION DESCRIPTORS

Section Title
Connections
Column
Title

Function

Legal Values

Port

Specify which port the device is connected to the
FieldServer

P1-P8 (with 232/485 converter), R1-
R2

1

Protocol

Specify protocol used

InfraTox or Infra-Tox

Baud*

Specify baud rate

19200 (Vendor limitation)

Parity*

Specify parity

None (Vendor limitation)

Data_Bits*

Specify data bits

8 (Vendor limitation)

Stop_Bits*

Specify stop bits

1


Example

// Client Side Connections

Connections
Port , Protocol , Baud

, Parity , Stop_Bits

R1

, InfraTox

, 19200 , None

, 1

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available

on specific hardware.