Page 12 of 17

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

6.3.3 Map Descriptor Example 1 Server using Data Array:

The following Map Descriptor enables this Driver to send data for all 8 sensors to the Node (DEV1) connected at the FieldServer. Refer to Section 4 for the
Data Array format.

The Driver can send Gas value messages, Alarm messages, Trouble messages and lock point messages. The driver can also be locked to send data for only one
particular sensor. In this example, if a valid (1-8) sensor number is inserted at offset 0 in the Data Array DA_CTL_R1, the driver will only send data for that
particular sensor. To disable the lock, insert an invalid (0 or >8) number.

// Server Side Map Descriptors

Map Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Length , Da_Byte_Name , Da_Byte_Oset
SMD1

, DA_R1

, 0

, Wrbc

, DEV1

, 100

, DA_CTL_R1

, 0


Driver will look
into this data array
to send Zellweger
message to
Zellweger 8
Channel Client.

Data Array Offset
indicates the
starting memory
location for the
Data to be sent to
the Node (DEV1).

Wrbc function makes
this Server an Active
Server. The Server
continuously writes
data for each sensor.

Client Node which
receives data from
the Server..

Length should be
sufficient to store
data for all
sensors for a
Node.

Name of Data
Array used to
lock sensor.
Driver will report
data for locked
sensor only.

The memory
location within the
Da_Byte_Name
Data Array at which
the user can put the
sensor number to
be locked.