Appendix C. Driver Error Messages
Message
Notes and Corrective Action
∼
TGM:#1 Err. Diagnostic #1.
If this message is printed an internal diagnostic has been 
generated. Contact FieldServer tech support for help. 
TGM:#2 Err. TGM_Function not 
specified. 
Each Map Descriptor must have the parameter called 
“TGM_Function” set. See section 4.4.2
2
TGM:#3 FYI. Use an Array 
called <%s> to expose 
diagnostics. 
This message may be ignored. For more information read 
Appendix C.1 
TGM: #4c Err. Bad format in 
latest area report. Discarding 
data. 
4a: The text string “CUR=” could not be found in the QLA 
report. 
4b: The text string “GAS=” could not be found in the QLA 
report. 
4c: The text string “STATUS=” could not be found in the 
QLA report. 
If the error is printed rarely and data is being stored 
correctly then the error probably arises from a corrupted 
message. If the error occurs frequently then it is possible 
that the report format has changed and the driver firmware 
may require an update. To facilitate the evaluation of the 
problem, take a serial communications log, ensuring at least 
one of the errors occurs during the log, and then contact 
Tech Support. 
TGM: #5 FYI. atmitgm.ini being 
used for malfunctions 
This message is printed to alert you to the fact that the 
malfunction list is being based on the contents of a TGM 
config file. Refer to Appendix B.7. If you expect the driver to 
be using this list, ignore the message. 
TGM: #6 FYI. You could have 
used a TGM config file to define 
malfunctions. Working with hard 
coded list. 
This message is printed to alert you to the possibility that 
the TGM config file can be used with this driver. Refer to 
Appendix B.7. 
TGM: #7 Err. Driver cannot 
write. MD=%s 
The Map Descriptor function has been set so that the driver 
will attempt to write to the TGM. Writing is not possible. 
Change the function to a read.
2
TGM: #8 Err. Array=%s too 
short. Act/Rqd=%d/%d 
This error is printed when the driver attempts to store data 
from the QLA report. Modify the length of the Data Array as 
discussed in section 4.1.
2
TGM: #9 FYI. Duplicate Gas 
Name=<%s>. 
Value has been updated 
from=%d to=%d 
This message may be safely ignored. It is printed to alert 
you to the fact that the driver has updated the Gas Name 
table so that default values have been modified. 
 
 
2
Modify the configuration CSV file. Download the modified file to the FieldServer and Reset the
FieldServer for the changes to take effect.