In the example below the gas name specified is ‘C2H5OH’ and it has been assigned an
index value of 7. It will be added to the table.

// Add a new gas name

Driver_Table

TGM_Gas_Name,

TGM_Gas_Index_Value,

Protocol

C2H5OH,

7,

TGM

Appendix B.5. Adding / Modifying Malfunction Strings

When an event is reported, the driver compares the “MAFLUN” events to those in the table
provided in Appendix A.2. The table can be modified or extended.

Add a section to the configuration file which is similar to the text found in the examples
below.

In the example below the gas name specified is ‘DISK NEARLY FULL’, an entry from the
existing list. When the driver finds the lines below, it will update the index value to 20.
Ensure the index value is less than 100.

// Change index value of existing malfunction.

Driver_Table

TGM_Malfunction_Name,

TGM_Malfunction_Index,

Protocol

DISK NEARLY FULL,

20,

TGM

In the example below the gas name specified is ‘DISK IS FULL’ and it has been assigned
an index value of 20. It will be added to the table.

// Add a new malfunction

Driver_Table

TGM_Malfunction_Name,

TGM_Malfunction_Index,

Protocol

DISK IS FULL,

20,

TGM