Thermatron controller board – Frymaster 2424G User Manual
Page 10
24G SERIES FLATBOTTOM GAS FRYERS
CHAPTER 1: SERVICE PROCEDURES
1-4
MELT CYCLE DISABLE
6
5
1
AC1
3
AC
2
3A
2A
7
8
9
1A
EX
T P
O
T
PROBE
10
11
2
COM
REL
A
Y
NO
12
13
NC
14
Not used
Line voltage enters the interface board at terminals 1 and 3. The temperature controls
(potentiometer) are connected to terminals 7, 8 and 9. The sensor probe circuit is connected to
terminals 10 and 11. The high-limit and gas valve routes through terminal 12. Terminals 2 and 13
are jumped out. Terminals 5 and 6 are the melt-cycle disable circuit. The melt cycle is enabled
unless terminals 5 and 6 are jumped out.
Thermatron Controller Board
See also other documents in the category Frymaster Fryers:
- D460G (2 pages)
- J3F (88 pages)
- TB14 (60 pages)
- Universal Holding Cabinet (53 pages)
- D80 Series (44 pages)
- CF SERIES J65X (50 pages)
- HCP (30 pages)
- GF40 (2 pages)
- GF14 (24 pages)
- FOOTPRINT E4 (88 pages)
- Enodis RE17TC (2 pages)
- Dean 52 Series (39 pages)
- CFESA BKSDU (13 pages)
- JCFX (76 pages)
- GEN II LOVTM BIELA14 (86 pages)
- Enodis FPRE14-7 (2 pages)
- UHC-HD (3 pages)
- FootPrint PRO FPP545 (2 pages)
- Dean SM35 (40 pages)
- FOOTPRINT RE80 (64 pages)
- 8196606 (24 pages)
- D680G (2 pages)
- 35 Series (40 pages)
- SR62 Series (14 pages)
- FPD65 (60 pages)
- LOV BIGLA30 (88 pages)
- FPD (100 pages)
- FOOTPRINT PRO SERIES 45 (50 pages)
- 1814 (10 pages)
- LOV M3000 (50 pages)
- 14 Series (78 pages)
- HD1814 SERIES HD1814G (46 pages)
- 1824/2424G (44 pages)
- YSCF14G (26 pages)
- HLZ18 (4 pages)
- FDP65 (60 pages)
- BIGLA30 (86 pages)
- BIELA14 (26 pages)
- BIRE14 (32 pages)
- FPH55 (2 pages)
- KSCF18G (68 pages)
- Enodis PF50S (2 pages)
- MH52 (115 pages)
- SM5020G (2 pages)