9. electrical service guide – Hobart Welding Products CYBERTIG 350LX User Manual
Page 21
OM-356 Page 17
3-9.
Electrical Service Guide
All values calculated at 60% duty cycle.
NOTE
50/60 Hertz Models
Without Power Factor Correction
Input Voltage
200
220
230
400
440
460
520
575
Input Amperes At Rated Output
129
117
112
65
58
56
49
45
Max Recommended Standard Fuse Or
Circuit Breaker Rating In Amperes
175
150
150
80
70
70
60
60
Min Input Conductor Size In AWG/Kcmil
4
4
4
8
8
8
8
10
Max Recommended Input Conductor
Length In Feet (Meters)
111
(34)
134
(41)
146
(45)
196
(60)
238
(72)
260
(79)
332
(101)
273
(83)
Min Grounding Conductor Size In AWG/
Kcmil
6
6
6
8
8
8
10
10
Reference: 1996 National Electrical Code (NEC)
S-0092-J
50/60 Hertz Models
With Power Factor Correction
Input Voltage
200
220
230
400
440
460
520
575
Input Amperes At Rated Output
98
89
85
49
44
43
37
34
Max Recommended Standard Fuse Or
Circuit Breaker Rating In Amperes
150
125
125
70
70
60
60
50
Min Input Conductor Size In AWG/Kcmil
4
4
4
8
8
8
10
10
Max Recommended Input Conductor
Length In Feet (Meters)
117
(36)
141
(43)
154
(47)
204
(62)
246
(75)
269
(82)
230
(70)
281
(86)
Min Grounding Conductor Size In AWG/
Kcmil
6
6
6
8
8
10
10
10
Reference: 1996 National Electrical Code (NEC)