Honeywell Local Operator Interface S7999B User Manual
Page 58
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
58
CH frost
protection
enable
Enabled
Disabled
25
30
DHW frost
protection
enable
Enabled
Disabled
Lead Lag
frost
protection
enable
Enabled
Disabled
Outdoor frost
protection
setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
(applicable for CH only)
Lead Lag
frost
protection
rate
___%
CH pump
frost overrun
time
___hour ___min ___sec
DHW pump
frost overrun
time
___hour ___min ___sec
Annunciation
enable
Enabled
Disabled
26
30
Annunciator
(1–8) location
01 - Annunciator 1
02 - Annunciator 2
03 - Annunciator 3
04 - Annunciator 4
05 - Annunciator 5
06 - Annunciator 6
07 - Annunciator 7
08 - Annunciator 8
PII - Pre-Ignition ILK
LCI - Load Control Input
ILK - Interlock
Annunciator
(1–8) short
name
Up to 3 characters
Annunciator
(1–8) name
Up to 20 characters
Table 61. Configurable Parameters. (Continued)
Parameter
Comment
Table
#
Page
#
PII enable
Enabled
Disabled
27
31
LCI enable
Enabled
Disabled
Interrupted
air switch
(IAS) enable
Enable during purge and
ignition
Disabled
Enable during purge
Interlock
(ILK) start
check enable
No ILK check
ILK check
ILK/IAS open
response
Recycle
Lockout
ILK bounce
detection
enable
Enabled
Disabled
Purge rate
proving
Fan Speed
High Fire Switch
None
Lightoff rate
proving
Fan Speed
Low Fire Switch
None
Prepurge
rate
RPM or %
28
31
Prepurge
time
0-600 seconds
0 = Not configured
Run
stabilization
time
0-600 seconds
0 = Not configured
Standby Rate RPM or %
Postpurge
rate
RPM or %
Postpurge
time
0-600 seconds
0 = Not configured
Forced
recycle
interval time
___hour ___min ___sec
Table 61. Configurable Parameters. (Continued)
Parameter
Comment
Table
#
Page
#