Honeywell AQUASTATIC L7224 User Manual

L7224 series oil electronic aquastat® controller, Adjusting settings, Display

background image

TECHNICIAN’S QUICK REFERENCE GUIDE

69-1957—1

L7224 Series

Oil Electronic

Aquastat® Controller

The following service procedure provides a quick overview for

L7224 Series Controllers. For more information, refer to form

69-1384.

On the L7224U the High Limit, High Limit Differential, Low Limit,

and Low Limit Differential can be adjusted to the settings

recommended by the boiler OEM.

Adjusting Settings

To discourage unauthorized changing of Aquastat® settings, a

procedure to enter the adjustment mode is required. To enter the

adjustment mode, press the UP, DOWN, and I buttons

simultaneously for three seconds. Press the I button until the

feature requiring adjustment is displayed:

HL—High Limit.

LL—Low Limit.

Ldf—Low Limit differential.

F - C—°F or °C.

Then press the UP and/or DOWN buttons to move the set point to

the desired value. After 60 seconds without any button inputs, the

control will automatically return to the READ mode.

To use the L7224U in a cold start boiler application, disable the

Low Limit function by pressing the UP arrow button, DOWN arrow

button and I buttons simultaneously for three seconds. Then push

the I button until LL is displayed. Then press the down arrow

button until OFF is displayed.

Display

In the RUN mode, the Aquastat® will flash “bt” (boiler temp)

followed by the temperature (i.e., 220), followed by °F or °C.

To read boiler settings, press the I key to read the parameter of

interest. For example, press I (HL) High Limit is displayed,

followed by a three-digit number, i.e., 220, followed by °F or °C.