Troubleshooting – FloAire Demand Control Ventilation System User Manual
Page 31

A0023662
May 2014 Rev.5
31
Troubleshooting
The following table lists causes and corrective actions for possible problems with this control. Review this
list prior to consulting manufacturer.
Troubleshooting Chart
Problem
Potential Cause
Corrective Action
Smoke Rollout of Hood
– Fans
don’t start-up when appliances
are ON
Dirty temperature sensor
Clean grease and dirt from
sensor
Poor Heat detection
Decrease duct Temperature
offset values
Improper hood installation
Check for proper hood overhang,
cross drafts or improper hood
design
Fans Spin Wrong Direction
3 phase Motor output wired
backward
Swap 2 of the 3 phase wires on
the output of the starter feeding
the motor
Light icon On but No Lights
Come On
Light bulbs are blown
Replace hood light bulbs
Loose wiring connection
Check light terminal block wiring
connections
Fan icon On but Fan
doesn’t
comes On
Broken fan belt
Replace fan belt
Loose wiring connection
Check wiring connections on
starters
VFD Fault List
0
No Fault
1
IGBT Temperature Fault
2
Output Fault
3
Ground Fault
4
Temperature Fault
5
Flying Start Fault
6
High DC BUS
7
Low DC BUS
8
Overload Fault
9
OEM Fault
10
Illegal Setup Fault
11
Dynamic Brake Fault
12
Phase Lost
13
External Fault
14
Control Fault
15
Start Fault
16
Incompatible Parameter Set
17
EPM Hardware Fault
18-27
Internal Fault
28
Remote Keypad Lost
29
Assertion Level Fault
30 - 33
Internal Fault
34
Comm. Module Failure
35 - 44
Network Fault
Refer to VFD manufacturer manual for further details.