beautypg.com

FloAire Demand Control Ventilation System User Manual

Page 11

background image

A0023662

May 2014 Rev.5

11

ACTECH SMV VFD CROSS-REFERENCE TABLE

Model Number

Volts

input

input

HP

Input

Amps

120VAC

Input

Amps

240VAC

Output

Amps

Breaker

120VAC

Breaker

240VAC

ESV751N01SXB571

120/

240V

X

1

16.6

8.3

4.2

25

15

ESV112N01SXB571

120/

240V

X

1.5

20

10

6

30

20

Input

Amps

Input

Amps

Breaker

Breaker

ESV371N02YXB571

240V

X

X

0.5

5.1

2.9

2.4

15

15

ESV751N02YXB571

240V

X

X

1

8.8

5

4.2

15

15

ESV112N02YXB571

240V

X

X

1.5

12

6.9

6

20

15

ESV152N02YXB571

240V

X

X

2

13.3

8.1

7

25

15

ESV222N02YXB571

240V

X

X

3

17.1

10.8

9.6

30

20

ESV402N02TXB571

240V

X

5

18.6

16.5

30

ESV552N02TXB571

240V

X

7.5

26

23

40

ESV752N02TXB571

240V

X

10

33

29

50

ESV113N02TXB531

240V

X

15

48

42

80

ESV153N02TXB531

240V

X

20

59

54

90

ESV751N04TXB571

480V

X

1

2.5

2.1

15

ESV112N04TXB571

480V

X

1.5

3.6

3

15

ESV152N04TXB571

480V

X

2

4.1

3.5

15

ESV222N04TXB571

480V

X

3

5.4

4.8

15

ESV402N04TXB571

480V

X

5

9.3

8.2

15

ESV552N04TXB571

480V

X

7.5

12.4

11

20

ESV752N04TXB571

480V

X

10

15.8

14

25

ESV113N04TXB531

480V

X

15

24

21

40

ESV153N04TXB531

480V

X

20

31

27

50

ESV183N04TXB531

480V

X

25

38

34

60

ESV223N04TXB531

480V

X

30

45

40

70

ESV751N06TXB571

600V

X

1

2

1.7

15

ESV152N06TXB571

600V

X

2

3.2

2.7

15

ESV222N06TXB571

600V

X

3

4.4

3.9

15

ESV402N06TXB571

600V

X

5

6.8

6.1

15

ESV552N06TXB571

600V

X

7.5

10.2

9

20

ESV752N06TXB571

600V

X

10

12.4

11

20

ESV113N06TXB531

600V

X

15

19.7

17

30

ESV153N06TXB531

600V

X

20

25

22

40

ESV183N06TXB531

600V

X

25

31

27

50

ESV223N06TXB531

600V

X

30

36

32

60