beautypg.com

A-4.2.8. genesis i non-isolated comms – Innotech Genesis V4 System User Manual

Page 94

background image

Installation Instructions for Innotech Genesis Systems

Edition 011100

A-13

Figure A-12. GENII MPI Modem and Printer Interface.

A-4.2.8.

Genesis I Non-Isolated Comms.

Because Genesis I Digital Controllers

do not have links between the RS485 ICs and the Comms terminals, the Comms terminals
are permanently connected to the Digital Controller Common and to Terminal 2.
Therefore, the screen(s) of the Comms cable(s) must be connected to Terminal 91 of only
one Digital Controller, as shown in the Figure A-13.

At looping connections the screens must be joined externally as shown in Figure A-13. The
screen must not be connected to the terminal at an end connection that is not the earthing
point for the screens.

For Digital Controllers supplied from one switchboard or mounted in one control panel, the
screen is earthed at one Digital Controller only.

MODEM

PC

PRINTER

A non-isolated MPI has the three DB connector shells and the pins shown connected

to COMMON. When a Printer or PC is connected, the RS485 Comms is earthed.

An isolated MPI has the three DB connector shells and the pins shown connected

to COMMON. When a Printer or PC is connected, the RS485 Comms are NOT earthed.

MODEM

PC

PRINTER

COMMS CABLE CONNECTION ON MPI

G+

G-

Gn

d

Gn

d

N+

N-

Socket on MPI viewed

from rear of MPI

Wh

it

e

Bl

ack

Re

d

Gre

e

n

Y

e

llow

Bl

ue

Plug and Cable viewed as

plugged into rear of MPI

N- (blue)
N+ (yellow)
Gnd (green)
Gnd (red)
G- (black)
G+ (white)

NOTE

On some units, wire colours

may be different than as