beautypg.com

Innotech Genesis V4 System User Manual

Page 42

background image

Installation Instructions for Innotech Genesis Systems

Edition 011100

3-16

or to terminate cable screens. Terminal 2 is the GND terminal for the analogue signal to the
controller; the cable screen and the screens from the four local analogue inputs should
terminate at this point. Terminal 3 connects to the appropriate

+

analogue input terminal on

the controller. The exact input terminal on the controller is indicated on the computer-
generated wiring diagram.

Analogue input terminals for the AIM are listed in Table 3-9.

Table 3-9. Analogue Input Module Input Signal Connections.

TERMINAL

SIGNAL

TERMINAL

SIGNAL

ACTIVE

REFERENCE

A

AI1+

B

AI1

C

AI2+

D

AI2

E

AI3+

F

AI3

G

AI4+

H

AI4

Particular care must be exercised in protecting the analogue signals from electromagnetic
interference of all types and in ensuring the proper termination of analogue cable screens.
Screens of input and output analogue signal cables and the analogue signal return lead to
the controller should be tied together at Terminal 2. Screening integrity must be maintained
at the input terminals of the module and not at entry points to the enclosure or at universal
terminal strips. Figure 3-7 provides an example of cable screen termination for an
installation containing two Analogue Input Modules and a Genesis II Digital Controller.

Figure 3-7. Analogue Input Module Wiring, Example.

1 2 3

A B C D E F G H I J

1 2 3

A B C D E F G H I J

A.I.M. #1

A.I.M. #2

LEM

RIBBON CABLE

TO

OTHER

LEMs

GENESIS II

DIGITAL CONTROLLER

SCREENS

TERMINALS

ANALOGUE INPUTS

32 33 34 35 36

19 20

21