2 control mounting guidelines, Ontrol, Ounting – Walker Magnetics SMART-D SERIES User Manual

Page 14: Uidelines

background image

O.S. WALKER Co., Inc. SMART-D Control

SMART D MANUAL DD14511L Rev. L, March 30, 2011

3-5

3.2 Control Mounting Guidelines

1. When any control (power section) is removed from its original enclosure or shipped without an

enclosure and installed in a customer supplied enclosure, the following specifications must be
met:

a. The air surrounding the panel on which the parts are located should not exceed 120°

Fahrenheit.

b. The air temperature must be measured:

1) With the control in the Full holding position;

2) After the control has been in operation for 30 minutes; and

3) With the chuck holding the largest load to be used.

2. When any control (power section) is to be placed in a secondary enclosure while still in its

original enclosure, the following specifications must be met:

a. With the control (power section) mounted in its original enclosure and then mounted in a

secondary enclosure, the air surrounding the original enclosure should not exceed 104°
Fahrenheit.

b. The air temperature must be measured:

1) With the control in the Full holding position;

2) After the control has been in operation for 30 minutes; and

3) With the chuck holding the largest load to be used.