3.2.8 Load Transfer Procedures Screen

Go to the SCC Master Menu and move the highlighted cursor to LOAD TRANSFER PROCE-

DURES. Note that this screen is displayed at the System Control Cabinet but is not required at the

UPS modules. Press the Select pad and the Load Transfer Procedures screen is displayed.
The Load Transfer Procedures screen contains instructions to transfer the critical load between the

UPS system and the bypass line. Comparisons of the UPS and bypass voltage, frequency and phase

synchronization are displayed along with transfer status messages and an indication of circuit

breaker overlap time. The metered parameter values on the Load Transfer Procedures screen are

updated at half-second intervals.
Refer to 3.4.3 - Load Transfer Procedures for more details.

Figure 41 Load transfer procedures screen

Item 1 - Voltage Comparisons: This chart shows the UPS and bypass voltage and frequency com-

parisons between each of the three phases. If the UPS and bypass voltages are not within specified

tolerances, a manual transfer is not permitted and TRANSFER PROHIBIT is highlighted.
The Voltage Adjust knob (push-to-turn), located on the SCC Operator Control Panel (Figure 10), is

used to match the UPS output voltage to the bypass voltage. When the UPS and bypass voltages

match within the specific tolerance, a manual transfer is possible and OK TO TRANSFER is high-

lighted.

Item 2 - Synchronization: This display shows the phase synchronization between the UPS output

and bypass power. If the phase displacement is outside of the tolerance, a manual transfer is not per-

mitted and TRANSFER PROHIBIT is highlighted.
During normal operation, the synchronization display should read UPS LEAD from zero to 4 degrees.
Item 3 - Status Messages: Three messages are constantly displayed here. Only the active message

is highlighted. If TRANSFER PROHIBIT is highlighted, manual transfers/retransfers cannot be

performed and automatic retransfers will not be initiated.
Item 4 - Manual Transfer Instructions: These instructions assist the operator in transferring the

critical load between the UPS system and the bypass line.
If the load is on the bypass line, step 2 on the screen will instruct you to press the UPS and Control

Enable buttons to retransfer the load from the bypass line to the UPS system.

!

CAUTION

The UPS output voltage responds very slowly to inputs from the Voltage Adjust knob.

Make small adjustments and wait several seconds each time for voltage to stabilize before

continuing.

OUTPUT VOLTS
OUTPUT AMPS
OUTPUT FREQUENCY
LOAD KVA
BYPASS VOLTS

A

380
530

380

DC

B

380
530

380

TIME

LOAD

349

C

380
530

380

HERTZ

50.0

NEXT FRAME

PREVIOUS FRAME

EXIT

UP :

DOWN :

SELECT :

HISTORY STATUS

MODULE-0

04/10/97

16:49:21

FRAME 36

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Output Ov-volts

OUTPUT VOLTS
OUTPUT AMPS
OUTPUT FREQUENCY
OUTPUT VOLTS
OUTPUT AMPS
BATTERY VOLTS
OUTPUT VOLTS
OUPUT AMPS
BATTERY AMPS
INPUT VOLTS
INPUT AMPS
OUPUT VOLTS
OUTPUT AMPS
LOAD KVA

A

380
410

380
410

380
410

0
0

380
410

DC

390

-583

B

380
410

380
410

380
410

0
0

380
410

TIME

0:01

LOAD

270

C

380
410

380
410

380
410

0
0

380
410

HERTZ

50.0

NEXT FRAME

PREVIOUS FRAME

EXIT

UP :

DOWN :

SELECT :

HISTORY STATUS

MODULE-0

01/17/98

11:21:59

FRAME 100

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Batt Discharging

Low Batt Warning

TRANSFER PROHIBIT

UPS LEAD

=

2 Deg

UPS

-

BYPASS

-

480

480

480

481

B-C

A-B

VOLTAGE COMPARISON

SELECT : MASTER MENU

OK TO TRANSFER

+30

ON UPS

60.0 Hz

479

C-A

FREQUENCY

MANUAL

TRANSFER INSTRUCTIONS

1.

Adjust the UPS voltage until it equals the
bypass voltage with the VOLTAGE ADJUST pot.

2.

If the OK TO TRANSFER message is highlighted,
simultaneously press the BYPASS and CONTROL ENABLE
buttons.

3.

Verify that the transfer was successful by checking the

breaker status on the "MONITOR/MIMIC" screen.

4.

Press the ALARM RESET button to clear alarms which
are no longer active

SYNCHRONIZATION

60.0 Hz

0

-30

480

1

2

4