Remote monitor, Table 6 scc and module remote monitor indications, Table 7 other alarms that activate summary alarms – Liebert 1000kVA User Manual
Page 57: Table 6, Scc and module remote monitor indications, Table 7, Other alarms that activate summary alarms

Operation
51
Figure 39 Monitor/Mimic display example: Continuous Duty Static Switch
Remote Monitor
The Remote Monitor Panel (optional) displays eight (8) alarms. These alarms are also available for
customer use through a set of contacts on a separate terminal board.
When the New Alarm, System Summary Alarm or Module Summary Alarm is activated, you can get
more information at the Operator Display Panel or through a remote terminal. Refer to 3.2.15 - Com-
The following alarms, as well as those listed above, will activate the System Summary Alarm or the
Module Summary Alarm.
Table 6
SCC and module remote monitor indications
SCC Remote Monitor Indications
Channel
Module Remote Monitor Indications
Load On UPS
CH1
Output CB Open
Load On Bypass
CH2
Battery CB Open
Battery Discharging
CH3
Battery Discharging
Low Battery Warning
CH4
Low Battery Warning
Overload
CH5
Control Failure
Ambient Overtemp
CH6
Ambient Overtemp
System Summary Alarm
CH7
Module Summary Alarm
New Alarm
CH8
New Alarm
Table 7
Other alarms that activate summary alarms
System Summary Alarm
Activation
Module Summary Alarm
Activation
Control Power Fail
Blower Failed
Emergency Off
Control Power Fail
Module Summary Alarm
DC Capacitor Fuse Blown
Output Over/Under Frequency
DC Ground Fault
Output Overvoltage
DC Overvoltage Shutdown
Output undervoltage
Emergency Off
Overload Transfer
Equipment Overtemperature
Static Switch Unable
Inverter Fault
Low Battery Shutdown
Overload
Overload Shutdown
Rectifier Fuse Blown
Reverse Power
BYPASS INPUT
∅
A-B
∅
B-C
∅
C-A
480V 480V 480V
60.0Hz
UPS INPUT PWR
∅
A-B
∅
B-C
∅
C-A
480V 480V 480V
UPS RATINGS
SCCB 1600
OUTPUT VOLTAGE
∅
A-B
∅
B-C
∅
C-A
480V 480V 480V
60.0Hz
LOAD
627 KVA / 502 KW
∅
A
∅
B
∅
C
755V 755V 755V
3 OF 3 MODULES
CONNECTED
REDUNDANT
MOD 1 ON LINE
MOD 2 ON LINE
MOD 3 ON LINE
CDSS
OK to Transfer
Static Switch Connected