Table 13 battery retorque values, Rack-mounted batteries, Table 14 battery voltage record – Liebert 1000kVA User Manual
Page 111: Table 13, Battery retorque values, Table 14, Battery voltage record

Maintenance
105
If you have a different model battery, contact Liebert Global Services for the required torque value.
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once
disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.
The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.
When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and
insulate the cables connected to the battery. Secure each battery shelf with retaining screws when
maintenance is complete.
Rack-Mounted Batteries
If the UPS system uses a battery other than a factory-supplied Matching Battery Cabinet, perform
maintenance on the battery as recommended in the battery manufacturer’s maintenance manual,
available on the manufacturer’s Web site.
Table 13
Battery retorque values
Battery
Manufacturer
Battery
Model No.
Retorque
Value
Dynasty
UPS12
-
270(FR)
32 lb
-
in.
UPS12
-
310(FR)
52 lb
-
in.
UPS12
-
370(FR)
52 lb
-
in.
UPS12
-
475(FR)
100 lb
-
in.
C&D Batteries
LS12
-
100 100
lb
-
in.
12G
-
17
100 lb
-
in.
Enersys
HX205
60 lb
-
in.
HX300
60 lb
-
in.
HX370
60 lb
-
in.
HX400
60 lb
-
in.
HX500
60 lb
-
in.
Table 14
Battery voltage record
Date
Float Voltage (Volts DC)
Nominal Voltage (Volts DC)
Ambient Temp. (°F)
(To be completed by Liebert Global Services customer engineer at time of start-up)