Figure 27 battery cycle monitoring summary screen, Operation 43 – Liebert 1000kVA User Manual
Page 49

Operation
43
The Summary screen (Figure 27) shows Total Number of Discharge Cycles, Accumulated Battery
Time, Accumulated Battery Amp Hours, Accumulated Battery Kilowatt Hours and Battery Tempera-
ture. During a battery discharge event, the screen changes to show information about the present dis-
charge cycle. The screen displays Active Cycle Time in place of Accumulated Battery Time and shows
Active Battery AH and Active Battery kWH instead of accumulated values.
Figure 27 Battery cycle monitoring summary screen
Figure 28 shows a typical detail screen for the 91-240 Seconds Discharge category. This information
can be collected remotely, through the optional communications board and modem, by a remote termi-
nal or a personal computer equipped with a modem and communications program. See 3.2.15 - Com-
munication Interfaces for more information.
Figure 28 Typical data on discharge cycles of 91 to 240 seconds duration during the recording period
NOTE
This information is applicable to systems with separate batteries for each module. If the
modules share a common battery, select one module to do the monitoring and disregard
the other(s).
7
15 min. 32 sec.
71
34
25°C / 77°F
Total No. of Cycles . . . . . . . . . . . . .
Accumulated Battery Time . . . . . . .
Accumulated Battery AH . . . . . . . .
Accumulated Battery KWH . . . . . . .
Battery Temperature . . . . . . . . . . . .
Battery Cycle Monitoring Summary
EXIT
SELECT :
© 1989-2003
EXIT
Event
Date
Time Duration Min. Volt Max. Amp Start KW Start Temp
15
4/12/95
10:31
235
477
110
70
68
12
3/25/95
20:21
98
479
97
37
65
9
3/13/95
7:35
139
467
173
69
67
5
2/07/95
17:22
199
478
95
40
70
2
11/24/94
12:33
95
477
83
39
69
Total 91-240 se c. Cycl 5
CURSOR UP
CURSOR DOWN
CHOOSE
UP :
DOWN :
SELECT :
© 1989-2003