4.3.3 Limited Life Components

Your Liebert UPS has a design life well in excess of 10 years. Well-maintained units can continue to

provide economic benefits for 20 years or more. Long-life components are used in your UPS wherever

practical and cost-effective. However, due to current component material and manufacturing technol-

ogy limitations, a few components in your Liebert UPS will wear out and require replacement in less

than 10 years.
The following limited-life components are utilized in your UPS system. To prevent a wear-out failure

of one of these components affecting your critical load operations, Liebert recommends these compo-

nents be periodically inspected and replaced before their expected wear-out life. Individual users may

have site-specific requirements that differ from these typical life expectations.

Power capacitors are considered “failed” when their measured capacitance is -5% below their name-

plate rating. Typically, storage batteries are “worn out” when their full-load reserve time is -20%

below rated. Site-specific battery plants may have different end-of-life requirements. Fans and blow-

ers typically will stop rotating or rotate slower than expected.
In most cases, replacement components must exactly match the original component specifications and

are not readily available from third-party component distributors. For assistance with your specific

component specifications, replacement component selection and sourcing, call 1-800-LIEBERT.
For customers using Liebert Global Services (LGS) Preventive Maintenance Services, periodic inspec-

tion of these components is part of this service, as well as recommending replacement intervals to cus-

tomers to avoid unanticipated interruptions in critical load operations.

Component

Expected Life

Replace in:

Power AC filter capacitors

> 7 years

(~62,000 hours)

5 to 6 years

Power DC filter capacitors

> 7 years

(~62,000 hours)

5 to 6 years

Low-profile fans

> 7 years

(~62,000 hours)

5 to 6 years

Squirrel-cage blowers

10 years

(~87,600 hours)

8 to 9 years

Air filters, disposable
(see also 4.3.2 - Air Filters)

1 to 3 years

Check four times

per year

Battery, lithium

Logic memory backup

10 years

(~87,600 hours)

8 to 9 years

Battery, storage

Lead-acid wet-cell
(user selection)

10 to 20

years

1 to 2 years

prior to end-of-life

Valve-regulated lead-acid
(VRLA)

5 years

3 to 4 years

10 years

6 to 8 years