beautypg.com

7 bypass breaker reset – Sanyo SANUPS E11A202U User Manual

Page 34

background image

− 31 −

11.7 Bypass Breaker Reset

CAUTION

Always power the UPS off before resetting the bypass breaker. Failure to do

so can cause electric shock. Be careful to avoid injury or electric shock.

If the bypass breaker trips, the red ALARM indicator lights and output from the output
terminals stops.
Proceed as follows to reset the bypass breaker.

Stop the inverter by pressing

and holding it for 1 second, and then set

MAIN MCCB to “OFF”.

Examine if there are neither a problem nor a trouble in the equipment of the load .

Press the bypass breaker on the back panel of the UPS.

Set MAIN MCCB to “ON”, and then start the UPS by pressing

and holding it

for 1 second.
For details about UPS startup, see §9.1 “UPS Startup (Normal Operation)”.

UPS back panel



Note

If you reset the bypass breaker while the UPS is powered on, the red ALARM indicator will

remain lit until you power the UPS off. Always power the UPS off before resetting the bypass
breaker.

Bypass breaker

This completes the bypass breaker reset.