beautypg.com

2 ups startup (battery power), Set the main sw on the back panel to “on – Sanyo SANUPS E11A202U User Manual

Page 23

background image

− 20 −

9.2 UPS Startup (Battery Power)

During a power outage, low voltage, or other trouble with the AC input power to the UPS, you
can supply power to the inverter output from the built-in batteries.








Return to the Normal Operation and batteries are charged.

Hold for about 6 seconds

Buzzer

Musical trill

LEDs

Green INPUT

Blinking

Green INV.ON/STAND BY

Off

Green OUTPUT

Off

after 1 to 2 seconds

Green INPUT

Blinking

Green INV.ON/STAND BY

Lit

Green OUTPUT

Lit

Press

and hold it until the buzzer sounds. Release it when

the buzzer sounds.

Check that MAIN MCCB on the back panel is set to “OFF”.

LEDs are all off.

Breaker is “OFF”

.

Set the MAIN SW on the back panel to “ON”.

Buzzer

Silent

LEDs

Green INPUT

Lit

Green INV.ON/STAND BY Lit

Green OUTPUT

Lit