7. Wiring

CAUTION

Check that input and output power plugs are firmly seated. Do not exceed the
rated capacity when connecting loads to the output terminals. Check that

plugs and cards are firmly seated in the external interfaces. Failure to observe

these precautions can result in electric shock, fire, or bodily injury.

The input power plug must be grounded. Failure to ground it can result in
electric shock.

7.1 UPS Wiring

Check that MAIN MCCB is in the “OFF” position.

Connect the INPUT power plug of the UPS to a

utility power outlet.







MODEL

Type of Input pulg

Note

E11A202U001

NEMA TYPE 5-20P

(seen from prong side)


When the AC input power is single-wire

grounded, always connect the ground

phase to the S terminal (phase) side on

the UPS.

E11A202U001J

NEMA TYPE L5-30P
(seen from prong side)

When the AC input power is single-wire

grounded, always connect the ground
phase to the S terminal (phase) side on

the UPS.

Switch is “OFF”.

To 3-prong grounded

utility power outlet

Length: a

t least

1.8 m

(a

t least

7.09 inches)

This figure shows E11A202U001.

As for E11A202U001J, shape and

the number of receptacles are

different.

E

R

(Or, N)

E

S(W)

(Or, N)