2 control panel and indicators – Sanyo SANUPS E11A202U User Manual

Page 13

background image

− 10 −

5.2 Control Panel and Indicators




Functions

No.

Label

Status display

Lit

Not lit

Slow blink

Fast

blink

LED0 INPUT Input power status

Normal input

Input error

LED1

OUTPUT UPS output power status Inverter operation OFF

Bypass operation

LED2 ECONOMY Operation

mode

Economy mode

operation (*1)

OFF (*3)

LED3

DOUBLE

CONVERSION Operation mode

Double conversion

mode operation (*2) OFF (*3)

LED4 BATT.LOW Battery status

Battery power low Battery power

normal

Battery exhausted

Load level 25%

Load 25% or more Load under 25%

LED5 25

Output voltage setting

100V (*4)

Setting other than

100V

100V setting (*4)

Load level 50%

Load 50% or more Load under 50%

LED6 50

Output voltage setting

110V (*4)

Setting other than

110V

110V setting (*4)

Load level 75%

Load 75% or more Load under 75%

LED7 75

Output voltage setting

115V (*4)

Setting other than

115V

115V setting (*4)

Load level 100%

Load 100% or more Load under 100%

LED8 100

Output voltage setting

120V (*4)

Setting other than

120V

120V setting (*4)

LED9

L

O

ADL

E

VEL

(%

)

O.L.

Overload display

Load 105% or more Load under 105%

None

LED10 ALARM Alarm display

Failure detected

No failure

INV.ON

STAND BY Inverter operation On/Off operation

LED11

INV.ON

STAND BY Inverter operation status Inverter operation

Off Bypass

operation

BATT.TEST Battery test

LED12 BATT.TEST Battery test

Result: Normal

Result: Error

Status:
Testing

CLEAR

Stop buzzer, clear result of battery test

1. Economy mode operation・・・・When power conditions are good, UPS supplies this power to the load.

2. Double conversion mode operation・・・・When power conditions fluctuate, UPS converts to the stable power, and

supplies to the load.

3. Active Filter Mode operation・・・・When load power fluctuates. Suppresses high frequencies generated by the load

and improves power factor.

When the green DOUBLE CONVERSION and the green ECONOMY are both off, the UPS is in Active Filter Mode.

4. The output voltage setting is displayed for about 5 seconds after the UPS is powered on (LED initialization display).

This manual uses a frame

to indicate switches. (Example: INV.ON/STAND BY ).

It also describes the color of the LED whenever it refers to an indicator on the control panel.

(Examples: Green INV.ON/STAND BY, red ALARM)




LED6

LED10

LED11

LED9

LED4

LED0 LED1 LED2 LED3

LED7

LED8

LED12

LED5

: Indicates a lit LED

In the illustrations in this manual

: Indicates a blinking LED