background image

4.7.3 OPC Server Example (Reading an analog input
value)

The following is an example of reading analog values from an I-87017 inserted in slot 0 of
an 8430/8830/8KE4/8KE8.

Step 1: Wire the8430/8830/8KE4/8KE8 and configure its network settings (IP, Mask,

Gateway)

Step 2: Run the VxComm Utility to create a virtual COM port (e.g. COM3) to map the

8430/8830/8KE4/8KE8

Step 3: Run the DCON Utility to configure the I/O modules

8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 63