Command

#AASiCj(data)

Description Sets the analog voltage output module data from the specified slot and

channel in the I-8000 unit. The data format is in engineering units only.
#AASiCj(data)[CHK](cr)
#

A delimiter character

AA

A 2-character HEX module address for the
specified I-8000 unit ,ranging from 01 to FFh

Si

The specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)

Cj

The specified channel number.
i-87022

Î j = 0 to 1

i-87024

Î j = 0 to 3

i-87026

Î j = 0 to 3

i-8024

Î j = 0 to 3

(data) A

decimal

value, always engineer unit

[CHK] A

2-character

checksum

Syntax

(cr)

Carriage Return (0x0D) to denote the end of
command

Valid Command

> [chk](cr)

Invalid Command

?AA[CHK](cr)

Any syntax or communication error may receive no response.
>

A delimiter for valid command

?

A delimiter for invalid command

AA

A 2-character HEX module address

[CHK]

A 2-character of checksum

(cr)

Carriage Return (0x0D) to denote the end of
response

Command

#01S3C1+09.000

Response

> (cr)

Example 1:

Description

This example sends the positive value +9.000V to
the Analog Data output Module in slot 3 and
channel 1 of the I-8000 unit at address 01h. The
response indicates the command is valid

Command

#01S3C1-05.000

Response

> (cr)

Example 2:

Description

This example sends the negative value -5.000V to
the Analog Data output Module in slot 3 and
channel 1 of the I-8000 unit at address 01h. The
response indicates the command is valid