#AASiCj
Command
#AASiCj
Description Reads the analog input or counter/frequency module data from
specified slot and the specified channel in the I-8000 unit.
#AASiCj[CHK](cr)
#
A delimiter character
AA
A 2-character HEX module address for the
specified I-8000 unit, ranging from 01 to FFh
Si
The specified slot number. i = 0 to 3 (4 slots) or
i = 0 to 7 (8 slots)
Cj
specified channel number.
i-87013
Î j = 0 to 3
i-8017H
Î j = 0 to 7
i-87017
Î j = 0 to 7
i-87018
Î j = 0 to 7
i-8080
Î j = 0 to 7
[CHK]
The 2-character of Checksum
Syntax
(cr)
Carriage Return(0x0D) for denote the end of the
command
Valid Command
>(data)[chk](cr)
Invalid Command
?AA[CHK](cr)
Any syntax or communication error may receive no response.
>
A delimiter for valid command
?
A delimiter for invalid command
AA
A 2-character HEX module address
(data)
A return string from RTD input module in
engineering mode.
[CHK] A
2-character
checksum
(cr)
Carriage Return (0x0D) to denote the end of the
response
Command
#01S3C0
Response
>+2.1234(cr)
Example
Description
The data read from the analog data input module
in slot 3 and channel 0 of the I-8000 unit at address
01h is +2.1234.
Notes: i-87013
Î 4-Channel RTD Analog Input Module
i-8017H
Î Fast 8-Channel mV/V/mA Analog Input Module
i-87017
Î 8-Channel mV/V/mA Analog Input Module
i-87018
Î 8-Channel mV/V/mA and Thermocouple Analog Input
Module
i-8080
Î 8-Channel Counter/Frequency Module
8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 73