If the chimney does not meet these termination requirements,
but all other requirements in the checklist can be met, it may
be possible for a mason to extend the chimney. If this will not
be practical, see Fix 1.

Wall or

Parapet

2' Min.

2' Min.

3' Min.

Chimney

10' or Less

10' or Less

2' Min.

3' Min.

Chimney

Termination 10 Feet Or Less From Ridge, Wall or Parapet

More than 10’

Wall or
Parapet

NOTE: No Height

above parapet

required when distance
from walls or parapet is

more than 10 feet.

Chimney

3’ Min.

More than 10’

10’

2” Min.

3’ Min.

Chimney

Height above any

roof surface within

10 feet horizontally.

Ridge

Termination More Than 10 Feet From Ridge, Wall or Parapet

C

HECK

2 - A

NY

S

OLID

OR

L

IQUID

F

UEL

A

PPLIANCES

V

ENTED

INTO

THIS

C

HIMNEY

C

HANNEL

Solid fuel appliances include fireplaces, wood stoves, coal fur-
naces, and incinerators.

Proper Chimney

Termination?

(Check 1)

Chimney channel

free of solid and

liquid fuel

appliances?

(Check 2)

Change venting

arrangements

(Fix 2)

Crown in good

condition

(Check 3)

Rebuild crown

(Fix 3)

and/or Reline

(Fix 4)

Reline

(Fix 4)

Reline

(Fix 4)

Cleanout free of

debris?

(Check 4)

Liner in good

condition?

(Check 5)

Reline

(Fix 4)

Dilution air

available?

(Check 6)

Complete the

installation.

(Check 7)

C

HECK

1 - P

ROPER

CHIMNEY

TERMINATION

.

A masonry chimney used as a vent for gas fired equipment
must extend at least three feet above the highest point where it
passes through the roof. It must extend at least two feet higher
than any portion of a building within a horizontal distance of 10
feet. In addition, the chimney must terminate at least 3 feet
above any forced air inlet located within 10 feet. The chimney
must extend at least five feet above the highest connected equip-
ment draft hood outlet or flue collar.