2. Water-Cooled Condenser

a) Connection to an Open Drain System

Condenser Water
Supply Inlet

Minimum Condenser
Water Supply Line Size

Condenser Drain
Outlet

Minimum Condenser
Drain Line Size

1/2" Female Pipe
Thread (FPT)

1/4" Nominal ID Copper
Water Tubing or Equivalent

1/2" Female Pipe
Thread (FPT)

1/4" Nominal ID Hard
Pipe or Equivalent

• A condenser water supply line shut-off valve and drain valve must be installed.

• In some areas, a back fl ow preventer may be required in the cooling water circuit.

• In order to maintain the proper high side pressure, the condenser water supply inlet

temperature must be in the 45°F to 90°F (7°C to 32°C) range.

Fig. 5

KM-151BWH

2-inch (5-cm) air
gap

Drain

Floor

Icemaker Water Supply
Inlet 1/2” FPT

Icemaker Drain
Outlet 3/4” FPT

Condenser Drain
Outlet 1/2” FPT

Condenser Water
Supply Inlet 1/2” FPT

To approved
fl oor drain

1/4” fall
per foot

Icemaker Water Supply
Line Shut-off Valve

Icemaker Water Supply
Line Drain Valve

Minimum 1/4” Nominal ID
Copper Water Tubing

Condenser Water Supply
Line Shut-off Valve

Condenser Water Supply
Line Drain Valve

Minimum 3/4” Nominal
ID Hard Pipe

Minimum 1/4” Nominal
ID Hard Pipe

Trap

Be sure there is suffi cient
extra water supply line and
drain line for the appliance
to be pulled out for service.

Separate piping to approved
drain. Leave a 2-inch (5-cm)
vertical air gap between the
end of each pipe and the
drain.