PIR APPLICATION GUIDE FOR TB7200 AND TB7300 SERIES THERMOSTATS

31

63-4526—01

11. TB7300 stand-alone fan coil application—3 levels of occupancy with dual PIR sensors

Sequence of operation:

At initial power-up, when the thermostat 24 Vac power supply is applied; the initial occupancy of the zone will be stand-by mode if

the PIR devices do not detect any movement.

As soon as a PIR device detects a movement or motion, the occupancy status switches to occupied and the occupied setpoints

are used. The room will then be in occupied mode until a door toggle is detected.

If a door toggle is detected, then the room switches to stand-by mode and the stand-by setpoints are used. If any occupants are

left in the room, local movements must be seen to resume the occupied mode.

While in stand-by mode, if no motion is detected in the zone for the entire unoccupied timer duration, then the room switches to

unoccupied mode and the unoccupied setpoints are used.

At anytime, if the PIR device detects a local movement or motion, the occupancy status switches to occupied and the occupied

setpoints are used.

Set-up and Configuration
Thermostat used

TB73x5X5014X (lodging models)

PIR used

BI1 configured for remote PIR sensor
and TB-PIR-FCU-L cover

BI2 Configuration

Door dry contact

Stand-by timer value

2.0 hours

Unoccupied timer value

6.0 hours

Network interface used

None, stand-alone

Remote PIR Sensor

Door Switch

Remote PIR Sensor

Door Switch

Unoccupied Time

= 6 Hours

Occupied

Stand-By

Unoccupîed

Time

Unoccupied Time Elapsed
= Unoccupied Mode

Initial State at

Power-Up = Stand-By

Always

Occupied

Door Open/Close
Toggle Detected