Beacon ii controller – Heatcraft Refrigeration Products II User Manual
Page 25
25
Beacon II Controller
System Defaults
Figure 15. Control Sensor And Piping
Table 5. System Defaults
Parameters
Code
Air
Electric
Refrigerant
rEF
R22
R404A
Box Temperature
bot
35°F
-10°F
Superheat
SUP
8°F
8°F
Slave Evaporator
SLA
No
No
No. of Defrosts Per Day
dFn
2
4
Defrost Fail-Safe Time
dFF
40 min.
30 min.
Defrost End Temperature
dFt
45°F
60°F
Defrost Delay Start Time
dFS
0 hrs.
0 hrs.
Alarm High Temperature
ALH
50°F
5°F
Alarm Low Temperature
ALL
30°F
-15°F
Alarm Time
ALt
60 min.
60 min.
Temperature Units
F-C
°F
°F