Beacon ii controller, Alarms, Clearing alarms – Heatcraft Refrigeration Products II User Manual
Page 23: Error indicator led
![background image](/manuals/95704/23/background.png)
23
Beacon II Controller
Alarms
Beacon II provides a set of dry contacts for use in signaling an alarm. These contacts can be connected to a
light, a buzzer, a bell, etc., which will be activated when an alarm condition occurs. When the Beacon II is
energized, the alarm contacts are OPENED. When an alarm condition is detected, the contacts are CLOSED.
Conditions under which the alarm contacts will close are:
•
High Box Temperature – LED Display:
A1
– Room temperature has exceeded the Alarm High
ALH
value
for the Alarm time
ALt
, programmed.
•
Low Box Temperature – LED Display:
A2
– Room temperature has dropped below the Alarm Low
ALL
value for the Alarm time
ALt
, programmed.
•
System Start-Up Failure – LED Display:
A3
– Compressor does not start after three tries. Four minutes
between each try.
•
Input Fault – LED Display:
A4
– Box Temp., Suction Temp., Pressure Transducer open or not installed.
•
Power Failure – Loss of power to the Evaporator.
ALARM CODES
A1
High Box Temp
A2
Low Box Temp
A3
System Start-Up Failure
Compressor does not start after 3 times.
(Four minutes between each try)
A4
Input Fault
Box Temp., Suction Temp., Pressure
Transducer open or not installed
Clearing Alarms
Alarms A1 - High Box Temp. and A2 - Low Box Temp. will clear automatically if the Box Temperature
decreases or increases to below or above the Alarm set-point temperature. Placing the system in the “Service
mode or turning off power will clear the A3 Alarm. Replacing the Room Sensor, Suction sensor, or Pressure
Transducer will clear the A4 Alarm.
Error Indicator LED
At initial power up, each Beacon II board checks for system errors. The system error check involves checking
the various temperature sensors to determine whether any of these sensors are shorted or open.
The system will pumpdown and cycle off and
will not restart
until the fault is cleared or the circuit breaker
reset, for the following conditions:
– Suction sensor shorted, open or not installed
– Room temperature sensor shorted or not installed
– Pressure Transducer open or not installed
The system will pumpdown, cycle off and
try to restart for three consecutive times
. Each try will be after
the 4 minutes “Hold Off” period, for the following fault conditions:
– Superheat too low
– High pressure or low pressure cutout
– Oil pressure
After the third try, the system will shut down and not try to restart. The Alarm contacts will be closed and an
alarm message displayed on the LED.
ERROR CODES
E1
– Room temperature sensor shorted, open or not installed
E2
– Defrost temperature sensor shorted, open or not installed
E3
– Suction temperature sensor shorted, open or not installed
E4
– Suction pressure transducer shorted, open or not installed
E5
– Outdoor temperature sensor shorted
E6
– Low superheat
E7
– Compressor shut down (high or low pressure switch open or oil pressure switch open).
E9
– Multi-in / multi-out wiring error