SPECIFICATIONS
Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers and fused
disconnects are to be mounted remote and wired by contractor. Sizes are based on the 2002 NEC table
310-16. Conduit size based on conductors plus ground wire sizing per Table C1 from Appendix C.
Only 6, 7 & 9 kW models can be field converted to single or three phase (open delta on 3 phase). Larger
branch circuit required than for balanced 3 phase of equal kW. Balanced 3 phase available, consult factory.
NOTE: 250 kcmil maximum wire size for terminal block.
kW
Volts*
Phase
Amp Draw
Breaker or
Copper
C o n d u i t
L1
L2
L3
Fuse Size
Wire Size
Size
13.5
208
1
65
65
-
90
3
1" (25 mm)
208
3
38
38
38
50
8
1/2" (13 mm)
240
1
56.3
56.3
-
90
3
1" (25 mm)
240
3
33
33
33
50
8
1/2" (13 mm)
480
3
16.3
16.3
16.3
30
10
1/2" (13 mm)
600
3
13
13
13
20
12
1/2" (13 mm)
15
208
1
72
72
-
90
3
1" (25 mm)
208
3
41.7
41.7
41.7
60
6
3/4" (19 mm)
240
1
62.5
62.5
-
90
3
1" (25 mm)
240
3
36.1
36.1
36.1
50
8
1/2" (13 mm)
380
3
23.0
23.0
23.0
30
10
1/2" (13 mm)
480
3
18.1
18.1
18.1
30
10
1/2" (13 mm)
600
3
14.5
14.5
14.5
20
12
1/2" (13 mm)
17.25
208
3
47.9
47.9
47.9
60
6
3/4" (19 mm)
18
208
1
86.5
86.5
-
125
1
1-1/4" (32 mm)
240
1
75
75
-
100
3
1" (25 mm)
240
3
43.4
43.4
43.4
60
6
3/4" (19 mm)
380
3
27.3
27.3
27.3
40
8
1/2" (13 mm)
480
3
21.7
21.7
21.7
30
10
1/2" (13 mm)
600
3
17
17
17
30
10
1/2" (13 mm)
24
208
1
115.4
115.4
-
150
1/0
1-1/4" (32 mm)
208
3
66.7
66.7
66.7
90
3
1" (25 mm)
240
1
100
100
-
125
1
1-1/4" (32 mm)
240
3
57.8
57.8
57.8
90
3
1-1/4" (32 mm)
380
3
38.0
38.0
38.0
50
8
1/2" (13 mm)
480
3
29.9
29.9
29.9
40
8
1/2" (13 mm)
600
3
23
23
23
30
10
1/2" (13 mm)
27
208
1
129.8
129.8
-
175
2/0
1-1/4" (32 mm)
208
3
75
75
75
100
3
1" (25 mm)
240
1
112.5
112.5
-
150
1/0
1-1/4" (32 mm)
240
3
65
65
65
90
3
1" (25 mm)
380
3
38.1
38.1
38.1
50
8
1/2" (13 mm)
480
3
32.5
32.5
32.5
50
8
1/2" (13 mm)
600
3
26
26
26
40
8
1/2" (13 mm)
30
208
1
144
144
-
200
3/0
1-1/2" (38 mm)
208
3
83.3
83.3
83.3
125
1
1-1/4" (32 mm)
240
1
125
125
-
175
2/0
1-1/2" (38 mm)
240
3
72.3
72.3
72.3
100
3
1" (25 mm)
380
3
45.7
45.7
45.7
60
6
3/4" (19 mm)
480
3
36
36
36
50
8
1/2" (13 mm)
600
3
28.9
28.9
28.9
40
8
1/2" (13 mm)
CIRCUIT BREAKER & FUSED DISCONNECT SWITCH SIZES - 13.5 TO 30 kW
(continued)