beautypg.com

Phase loss monitor, Recommended refrigerant piping practices, Refrigerant pipe support – Heatcraft Refrigeration Products H-IM-FL1A User Manual

Page 7

background image

7

Phase Loss Monitor

The combination phase sequence and loss monitor relay

protects the system against phase loss (single phasing), phase

reversal (improper sequence) and low voltage (brownout).

When phase sequence is correct and full line voltage is present

on all three phases, the relay is energized as the normal

condition indicator light glows.
NOTE: If compressor fails to operate and the normal condition

indicator light on the phase monitor does not glow, then the

supplied electrical current is not in phase with the monitor. This

problem is easily corrected by the following steps:

1. Turn power off at disconnect switch.

2. Swap any two of the three power input wires.

3. Turn power on. Indicator light should glow and

compressor should start.

4. Observe motors for correct rotation.

Recommended Refrigerant Piping Practices

The system as supplied by Heatcraft Refrigeration Products,

was thoroughly cleaned and dehydrated at the factory. Foreign

matter may enter the system by way of the evaporator to

condensing unit piping. Therefore, care must be used during

installation of the piping to prevent entrance of foreign matter.
Install all refrigeration system components in accordance with

applicable local and national codes and in conformance with

good practice required for the proper operation of the system.
The interconnecting pipe size is not necessarily the same size

as the stub-out on the condensing unit or the evaporator.
The following procedures should be followed:

(a) Do not leave dehydrated compressors or filter-driers on

condensing units open to the atmosphere any longer

than is absolutely necessary.

(b) Use only refrigeration grade copper tubing, properly

sealed against contamination.

(c) Suction lines should slope 1/4" per 10 feet towards the

compressor.

(d) Suitable P-type oil traps should be located at the base of

each suction riser of four (4) feet or more to enhance oil

return to the compressor.

(e) For desired method of superheat measurement,

a pressure tap should be installed in each evaporator

suction line in the proximity of the expansion valve bulb.

(f) When brazing refrigerant lines, an inert gas should

be passed through the line at low pressure to

prevent scaling and oxidation inside the tubing.

Dry nitrogen is preferred.

(g) Use only a suitable silver solder alloy on suction and

liquid lines.

(h) Limit the soldering paste or flux to the minimum

required to prevent contamination of the solder

joint internally. Flux only the male portion of the

connection, never the female. After brazing, remove

excess flux.

(i) If isolation valves are installed at the evaporator, full port

ball valves should be used.

Figure 4. Example of Pipe Support

Refrigerant Pipe Support

1. Normally, any straight run of tubing must be supported

in at least two locations near each end of the run. Long

runs require additional supports. The refrigerant lines

should be supported and fastened properly. As a guide,

3/8 to 7/8 should be supported every 5 feet; 1-1/8 and

1-3/8 every 7 feet; and 1-5/8 and 2-1/8 every 9 to 10

feet.

2. When changing directions in a run of tubing, no corner

should be left unsupported. Supports should be placed a

maximum of 2 feet in each direction from the corner.

3. Piping attached to a vibrating object (such as a

compressor or compressor base) must be supported

in such a manner that will not restrict the movement

of the vibrating object. Rigid mounting will fatigue the

copper tubing.

4. Do not use short radius ells. Short radius elbows have

points of excessive stress concentration and are subject

to breakage at these points.

5. Thoroughly inspect all piping after the equipment

is in operation and add supports wherever line vibration

is significantly greater than most of the other piping.

Extra supports are relatively inexpensive as compared

to refrigerant loss.

Figure 5. Condensing Unit / Compressor to Wall Support.