beautypg.com

System balancing - compressor superheat, Operational check out – Heatcraft Refrigeration Products H-IM-FL1A User Manual

Page 13

background image

13

NOTE: All adjustable controls and valves must be field

adjusted to meet desired operation. There are no

factory preset controls or valve adjustments.

System Balancing - Compressor Superheat

IMPORTANT: In order to obtain the maximum capacity

from a system, and to ensure trouble-

free operation, it is necessary to balance

each and every system.

This is extremely important with any refrigeration system.
The critical value which must be checked is suction superheat.
Suction superheat should be checked at the compressor

as follows:

1. Measure the suction pressure at the suction service

valve of the compressor and determine the saturation

temperature corresponding to this pressure from a

“Temperature-Pressure” chart.

2. Measure the suction temperature of the suction line

about one foot back from the compressor using an

accurate thermometer.

3. Subtract the saturated temperature from the actual

suction line temperature. The difference is superheat.

Too low a suction superheat can result in liquid being returned

to the compressor. This will cause dilution of the oil and

eventual failure of the bearings and rings or in the extreme

case, valve failure.
Too high a suction superheat will result in excessive discharge

temperatures which cause a break down of the oil and results

in piston ring wear, piston and cylinder wall damage.
It should also be remembered that the system capacity

decreases as the suction superheat increases. For maximum

system capacity, suction superheat should be kept as low as

is practical. Copeland mandates a minimum superheat of

20˚F at the compressor. Heatcraft Refrigeration Products

recommends that the superheat at the compressor be

between 30˚F and 45˚F.
If adjustments to the suction superheat need to be made,

the expansion valve at the evaporator should be adjusted.

Operational Check Out

After the system has been charged and has operated for at

least two hours at normal operating conditions without any

indication of malfunction, it should be allowed to operate

overnight on automatic controls. Then a thorough recheck of the

entire system operation should be made as follows:

(a) Check compressor discharge and suction pressures.

If not within system design limits, determine why and

take corrective action.

(b) Check liquid line sight glass and expansion valve

operation. If there are indications that more refrigerant

is required, leak test all connections and system

components and repair any leaks before adding

refrigerant.

(c) Thermostatic expansion valves must be checked for

proper superheat settings. Feeler bulbs must be in

positive contact with the suction line and should be

insulated. Valves set at high superheat will lower

refrigeration capacity. Low superheat promotes liquid

slugging and compressor bearing washout.

(d) Using suitable instruments, carefully check line voltage

and amperage at the compressor terminals. Voltage

must be within 10% of that indicated on the

condensing unit nameplate. If high or low voltage is

indicated, notify the power company. If amperage draw

is excessive, immediately determine the cause and

take corrective action. On three phase motor

compressors, check to see that a balanced load is

drawn by each phase.

(e) The maximum approved settings for high pressure

controls on Heatcraft air cooled condensing equipment

is 400 psig. On air cooled systems, check as follows:

Disconnect the fan motors or block the condenser

inlet air. Watch high pressure gauge for cutout point.

Recheck all safety and operating controls for proper

operation and adjust if necessary.

(f) Check winter head pressure controls for pressure

setting.

(g) Check crankcase heater operation if used.

(h) Install instruction card and control system diagram for

use of building manager or owner.