4-10. Serial Number And Rating Label Location

The serial number and rating information for this product is located on the back. Use rating label to determine input power requirements and/or rated
output. For future reference, write serial number in space provided on back cover of this manual.

4-11. Connecting 1-Phase Input Power For 240 VAC

803 766-B / Ref. 802 443-A

!

Installation

must

meet

all

National and Local Codes ï have

only qualified persons make this

installation.

!

Disconnect and lockout/tagout

input power before connecting

input conductors from unit.

!

Always connect green or green/

yellow conductor to supply

grounding terminal first, and never

to a line terminal.

1

Black And White Input Conductor
(L1 And L2)

2

Green Or Green/Yellow Grounding
Conductor

3

Input Power Cord.

4

Disconnect Device (switch shown in
the OFF position)

5

Disconnect Device Grounding
Terminal

6

Disconnect Device Line Terminals

Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.

Connect input conductors L1 and L2 to
disconnect device line terminals.

7

Over-Current Protection

Select type and size of over-current
protection using Section 4-8 (fused
disconnect switch shown).

8

Receptacle (NEMA 6-50R)
Customer Supplied

Close and secure door on disconnect
device. Remove lockout/tagout device,
and place switch in the On position.

4

3

L1

L2

1

=GND/PE Earth Ground

2

1

5

6

7

Tools Needed:

L1

L2

240 VAC, 1

8