Troubleshooting – Heat & Glo Fireplace EXCLAIM-36T-C User Manual
Page 32

Heat & Glo • EXCLAIM-36C Woodburning Fireplace • 4013-093 Rev G • 08/06
32
10
10
Troubleshooting
Another appliance in
home also exhausting
air (furnace, fan,
dryer, etc.)?
Air register from
furnace near
fireplace?
Doors opening
and closing?
Window closed
for start-up?
Outside air
closed?
Overhead fan
operating?
Overhanging
tree?
Bird's nest
or leaves in
termination
cap?
Structural
changes in
chimney area?
Creosote buildup
in flue?
Damper closed?
Stron
g w
in
ds
a
ro
un
d c
himney
term
ina
tio
n?
Unsealed
can lights?
Figure 10.1 Factory-built Fireplaces: Troubleshooting
This
¿ replace will operate correctly only if adequate ventila-
tion is provided to allow proper draft to the
¿ replace system.
Hearth & Home Technologies assumes no responsibility for
the improper performance of the
¿ replace system caused
by inadequate draft due to environmental conditions, down
drafts, tight sealing construction of the structure, or mechan-
ical exhausting devices which will create a negative air pres-
sure within the structure where the
¿ replace is located.
A. Understanding Vent Problems
If smoke spillage occurs from a
¿ replace opening when the
door is open and the proper chimney height,
À ue size, and
con
¿ guration requirements for the installation have been
met, there is either a leakage in the
À ue, a blockage in the
À ue, or some condition is in effect to draw smoke from the
¿ replace into the house. Understanding and differentiating
the conditions which can cause each of these kinds of spill-
age problems is essential to their solution.
• Flue
Leakage
Check for improperly connected
À ue joints or a damaged
À ue joint in the chimney system. Such leakage would
reduce draft (air would be drawn in through the leaks rather
than through the
¿ replace). The result might be dif¿ cult
start-up and smoky
¿ res that might spill if other adverse
draft conditions accompany this problem.
• Flue
Blockage
The damper should be open.