beautypg.com

Electrical service guide, Extension cord data, 7. electrical service guide – Hobart Welding Products 625 User Manual

Page 17: 8. extension cord data

background image

.

A complete Parts List is available at www.HobartWelders.com

OM-926 Page 13

4-7.

Electrical Service Guide

50/60 Hz Single Phase

Input Voltage

208

230

Input Amperes At Rated Output

33

30

Max Recommended Standard Fuse Rating In Amperes

Cricuit Breaker

1

, Time-Delay

2

40

35

Normal Operating

3

50

45

Min Input Conductor Size In AWG

4

10

10

Max Recommended Input Conductor Length In Feet (Meters)

80

(24)

98

(30)

Min Grounding Conductor Size In AWG

4

10

10

Reference: 2005 National Electrical Code (NEC) (including article 630)

1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

Y

Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.

4-8.

Extension Cord Data

When calculating max. cord length, remember to include conductor length from
line disconnect device to input power receptacle.

NOTE

Input Voltage

Input Power

Phase

Hertz

Fuse Size Or

Circuit Breaker Rating

Conductor Size

Max. Cord Length

208 V

1

50/60

Time-Delay

2

40 A

Normal Operating

3

50 A

10 AWG

80 ft (24 m)

230 V

1

50/60

Time-Delay

2

35 A

Normal Operating

3

45 A

10 AWG

98 ft (30 m)

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose − no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).