beautypg.com

Extension cords, Nameplate amperes – Harbor Freight Tools BELT SANDER - 1 X 30 INCHES 2485 User Manual

Page 7

background image

Page 7

SKU 02485

for technical questions, please call 1-800-444-3353.

Double insulated tools may be used in either of the 120 volt outlets shown in the pre-
ceding illustration.

(see Outlets for 2-prong plug.)

extensiOn cOrds

Grounded tools require a three wire extension cord. Double Insulated tools can use
either a two or three wire extension cord.

As the distance from the supply outlet increases, you must use a heavier gauge exten-
sion cord. Using extension cords with inadequately sized wire causes a serious drop
in voltage, resulting in loss of power and possible tool damage.
(see table A.)

The smaller the gauge number of the wire, the greater the capacity of the cord. For
example, a 14 gauge cord can carry a higher current than a 16 gauge cord.
(see table A.)

When using more than one extension cord to make up the total length, make sure each
cord contains at least the minimum wire size required.

(see table A.)

If you are using one extension cord for more than one tool, add the nameplate

amperes

and use the sum to determine the required minimum cord size.
(see table A.)

If you are using an extension cord outdoors, make sure it is marked with the suffix “W-
A” (“W” in Canada) to indicate it is acceptable for outdoor use.

Make sure your extension cord is properly wired and in good electrical condition. Al-
ways replace a damaged extension cord or have it repaired by a qualified electrician
before using it.

Protect your extension cords from sharp objects, excessive heat, and damp or wet
areas.

recOMMended MiniMuM wire gAuge fOr extensiOn cOrds*

(120 Or 240 VOlt)

nAMeplAte

AMperes

(at full load)

extensiOn cOrd lengtH

25 feet

50 feet

75 feet

100 feet 150 feet

0 – 2.0

18

18

18

18

16

2.1 – 3.4

18

18

18

16

14

3.5 – 5.0

18

18

16

14

12

5.1 – 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1 – 16.0

14

12

10

-

-

16.1 – 20.0

12

10

-

-

-

tAble A

* based on limiting the line voltage drop to five volts at 150% of the rated amperes.

2.

1.

2.

3.

4.

5.

6.

7.

8.