Top vent - vertical termination no elbow, 3 ft. min. (914 mm) – Heat & Glo Fireplace Heat & Glo Gas Fireplace ESC-42ST User Manual

Page 29

background image

Heat & Glo • ESC-42ST • 2146-900 Rev. Q • 4/13

29

2. Top Vent - Vertical Termination

No Elbow

Figure 7.6

V

1

V

1

= 50 ft. Max. (15.2 m)

V

1

= 3 ft. Min. (914 mm)

Figure 7.7

V

1

H

1

V

2

2 ft

610 mm

1 ft

305 mm

*

3 ft

914 mm

3 ft

914 mm

*

4 ft

1.2 m

4 ft

1.2 m

*

5 ft

1.5 m

9 ft

2.7 m

*

6 ft

1.8 m

12 ft

3.7 m

*

V

1

+ V

2

+ H

1

= 50 ft (15.2 m) Max.

*No specifi c restrictions on this value EXCEPT

V

1

+ V

2

+ H

1

cannot exceed 60 ft (18.3 m).

After V

1

= 6 ft, then H

1

Max.= V

1

x 2

FLUE RESTRICTOR

NOTE: Flue Restrictor ships in
manual bag assembly.

Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.

Note: Must have a 24 inches minimum
vertical vent before attaching any
elbow to the appliance.

Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.

Note: Must have a 24 inches minimum
vertical vent before attaching any
elbow to the appliance.