B. Clearances

WARNING! Risk of Fire! You must comply with all minimum air space clearances to combustibles as specifi ed in Fig-
ure 6.2. DO NOT pack required air spaces with insulation or other materials.

Heatilator • CL36D, CR36D • 12538 • Rev T • 09/08

(insulation)

0 in. to level

of standoffs

Attic

Insulation

Shield

(ceiling)

(roof)

(attic)

(ceiling)

Ceiling Firestop

Offset/Return (secured

with hanger straps)

Storm Collar

Roof Flashing

1/2 in. (13 mm) to back &

side of appliance

Must have 2 in. (51 mm)

minimum clearance

to header

0 in.

to floor

2 in. (51 mm) min.

Shaded areas

represent

2 in. (51 mm) min.

air space clearance

required around pipe

Chimney air kit

attached here (not shown)

Figure 6.2 Clearances to Combustible Materials

Note: Chimney air kit is not shown, but is required in Canada.